Note: The nominal output value for the various output ranges are designated in the 

following order:  (0 to 20 mA, 4 to 20 mA, 0 to 10 VDC)

The Basic Calibration should only be performed with an ambient temperature 

between 21°C and 29°C. The Basic Calibration was performed on the unit at the 

factory and generally does not need to be done again. This procedure initializes the 

unit by calibrating the input, and the Ice Point Compensation. The Basic Calibration 

should be performed only if a condition exists as described in the “Unit Malfunction” 

section. After completion of this calibration, the unit needs to be scaled in Field 

Calibration. The Basic Calibration procedure is described below. 

Note: To abort this calibration and reset to the previous settings, set the BASIC CAL 

switch(#3) OFF prior to the final setting of the OUTPUT CAL switch (Step 4.17) 

and turn off power for 5 seconds. Then turn on power and the previous settings will 

be loaded.

4.1  Connect a precision mV source with an accuracy of 0.02% to Terminal #7 (TC+ 

Input) and Terminal #8 (TC- Input). Set the ICE PT EN/DIS switch (#4), 

RANGE (#9&#10), TYPE (#6, #7, and #8), OUTPUT CAL (#1), and FIELD 

CAL (#2) switches OFF. Set the BASIC CAL switch (#3) ON.

4.2  Apply power and allow a 30 minute warm-up period. [Output goes to -0.9 mA, 

3.4 mA, or -0.5 V nominal]

4.3  Set the OUTPUT CAL switch (#1) ON and then OFF. 

4.4  Input -9 mV and wait 5 seconds.

4.5  Set the OUTPUT CAL switch (#1) ON and then OFF.

4.6  Input 6 mV and wait 5 seconds.

4.7  Set the OUTPUT CAL switch (#1) ON and then OFF.

4.8  Input 22 mV and wait 5 seconds.

4.9  Set the OUTPUT CAL switch (#1) ON and then OFF.

4.10 Input 41mV and wait 5 seconds.

4.11 Set the OUTPUT CAL switch (#1) ON and then OFF.

4.12 Input 63 mV and wait 5 seconds.

4.13 Set the OUTPUT CAL switch (#1) ON and then OFF.

4.14 Input 77 mV and wait 5 seconds.

4.15 Set the OUTPUT CAL switch (#1) ON and then OFF.
4.16 Ice Point Calibration. 

a. If ice point calibration is not desired, go to step 4.17.

b. To Enable ice point calibration, set the FIELD CAL switch (#2) ON.

1. Connect a precision thermometer (accuracy of  0.1°C) to the unused 

terminal beside the TC Input terminals. 

2. Allow 5 minutes for the temperature to equalize.

3. Using the temperature indicated by the precision thermometer, input an 

equivalent 1 mV/°C signal to the TC Input terminals.

4.17 Set the OUTPUT CAL switch (#1) ON and then OFF.

4.18 Set the BASIC CAL switch (#3) and FIELD CAL switch (#2) OFF. [Output 

increases to -0.8 mA, 3.5 mA, or -0.4 V nominal, or more]

4.19 Perform a Field Calibration. (See Section 1.0)

1 2 3 4 5 6 7

9

8

10

ON

1 2 3 4 5 6 7

9

8

10

ON

1 2 3 4 5 6 7

9

8

10

ON

1 2 3 4 5 6 7

9

8

10

ON

1 2 3 4 5 6 7

9

8

10

ON

2

1

ON

4

3

5 6 7 8 9 10

ON

3

1 2

5

4

6 7 8 9 10

ERROR

POWER

VDC+

10

TC+

7

V+

4

I+

1

VDC-

TC-

12

11

9

8

6

5

V-

3

2

I-

POWER SUPPLY

9 to 32 VDC

+

-

VOLTAGE METER

OR

CURRENT METER

ADJUSTABLE

MILLIVOLT

SOURCE

PRECISION

THERMOMETER

Basic Calibration Wiring

Step 4.1

Steps 4.3 to 4.15

Step 4.16

Step 4.17

Step 4.18

4.0 Basic Calibration

Note: The nominal output value for the various output ranges are designated in the 

following order:  (0 to 20 mA, 4 to 20 mA, 0 to 10 VDC)

The Ice Point Calibration should only be performed with an ambient temperature 

between 21°C and 29°C. This Calibration was performed on the unit at the factory 

during the Basic Calibration and generally does not need to be done again. The Ice 

Point Compensation can be adjusted through this calibration. The Ice Point Calibration 

procedure is described below.

Note: Calibration can be aborted by setting the BASIC CAL switch(#3) OFF prior to 

the setting of the OUTPUT CAL switch OFF. (Step 3.6)

3.1  Connect a precision mV source with an accuracy of 0.02% to Terminal #7 TC+ 

Input and Terminal #8 TC- Input. Set the OUTPUT CAL switch (#1) and ICE PT 

EN/DIS switch (#4) OFF. Set the BASIC CAL (#3) and FIELD CAL (#2) 

switches ON. The positions of switches #5 thru #10 are not relevant for this 

calibration procedure.

3.2  Connect a precision thermometer (accuracy of 0.1°C) to the unused terminal (#9) 

beside the TC Input terminals. 

3.3  Apply power and allow a 30 minute warm-up period. [Output goes to -0.9 mA, 

3.4 mA, or -0.5V nominal]

3.4  Using the temperature indicated by the precision thermometer, input an equivalent 

1 mV/°C signal to the TC Input terminals and wait 5 seconds.

3.5  Set the OUTPUT CAL switch (#1) ON and then OFF.

3.6  Set the BASIC CAL switch (#3) and FIELD CAL switch (#2) OFF. [Output 

increases to -0.8 mA, 3.5 mA, or -0.38 V nominal, or more]

1 2 3 4 5 6 7

9

8

10

ON

1 2 3 4 5 6 7

9

8

10

ON

1 2 3 4 5 6 7

9

8

10

ON

ON

1 2 3 4 5 6 7

9

8

10

Step 3.1

Step 3.5

Step 3.5

Step 3.6

ERROR

POWER

VDC+

10

TC+

7

V+

4

I+

1

VDC-

TC-

12

11

9

8

6

5

V-

3

2

I-

POWER SUPPLY

9 to 32 VDC

+

-

VOLTAGE METER

OR

CURRENT METER

ADJUSTABLE

MILLIVOLT

SOURCE

PRECISION

THERMOMETER

Ice Point Calibration Wiring

3.0 Ice Point Calibration

OUTPUT CAL

FIELD CAL

BASIC CAL

ICE PT DIS/EN

OPEN SEN DN

RANGE

RANGE

DIP SWITCH SETTINGS:

ON = 1

OFF = 0

TYPE

TC
TC TYPE

MODEL ITMA

9-32 VDC

ERROR

POWER

VDC+

10

TC+

7

V+

4

I+

1

VDC-

TC-

12

11

9

8

6

5

V-

3

2

I-

4

2
1

3

7

5

6

8

10

9

Содержание ITMA

Страница 1: ...ment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired SPECIFICATIONS 1 POWER 9 to 32 VDC 1 75 W The power supply must have 300 mA for 200...

Страница 2: ...rols and heaters etc The cables should be run through metal conduit that is properly grounded This is especially useful in applications where cable runs are long and portable two way radios are used i...

Страница 3: ...e case and cut the wire jumper The jumper is located to the left side of the board as shown in the drawing POWER Connect DC power to terminals 10 and 12 observing proper polarity Be certain DC power i...

Страница 4: ...en turn on power and the previous settings will be loaded Field Calibration with a Thermocouple Calibrator 1 1 Enable the Ice Point Compensation on the Thermocouple Calibrator and set it to the Thermo...

Страница 5: ...Output increases to 0 8 mA 3 5 mA or 0 4 V nominal or more 4 19 Perform a Field Calibration See Section 1 0 1 2 3 4 5 6 7 9 8 10 ON 1 2 3 4 5 6 7 9 8 10 ON 1 2 3 4 5 6 7 9 8 10 ON 1 2 3 4 5 6 7 9 8 1...