2

Relative Humidity

: Less than 85% RH (non-condensing)

Span

: The input span can be set to a min. of 1/8 of the full scale range, 

anywhere within that range.

Thermocouple Accuracy for each type and the corresponding ranges

:

9. 

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range

: -25°C to 75°C (-13°F to 167°F)

Storage Temperature Range

: -40 to 85°C (-40°F to 185°F)

Operating and Storage Humidity

: 85% max. relative humidity (non-

condensing) from -25°C to 75°C.

Vibration to IEC 68-2-6

: Operational 5-150 Hz, 2 g

Shock to IEC 68-2-27

: Operational 30 g

Altitude

: Up to 2000 meters

10.

 MOUNTING

: Universal mounting foot for attachment to standard DIN 

style mounting rails, including top hat (T) profile rail according to EN50022 

-35 

×

 7.5 and -35 

×

 15, and G profile rail according to EN50035 - G32.

11.

 CONNECTION

:

 

Compression type terminal block

12.

 CONSTRUCTION

: High impact black plastic case

13.

 CERTIFICATIONS AND COMPLIANCES

CE Approved

EN 61326-1 Immunity to Industrial Locations

Emission CISPR 11 Class B

IEC/EN 61010-1

RoHS Compliant

Refer to the EMC Installation Guidelines section of this bulletin for 

additional information.

14.

 WEIGHT

: 4.02 oz. (114.0 g)

FUNCTION DESCRIPTIONS

Open Sensor Detection

The output can be set to go Upscale or Downscale for the detection of an 

open sensor. The nominal values for each output range are listed under TC 

Break Detection in the Specifications section. This setting is always active, so 

changes to the setting are effective immediately.

Ice Point Compensation

The Ice Point Compensation for the thermocouple sensors can be enabled (DIP 

Switch OFF) or disabled (DIP Switch ON). The mV sensor input is not affected 

by this setting. Generally, the Ice Point Compensation is always enabled.

Unit Malfunction

If the unit has scaling problems (output remains at -0.5 mA, 3.5 mA, or -0.5 

VDC nominal), check the ERROR LED on the front of the unit. An E

2

PROM 

problem is indicated when the ERROR LED is on. If the ERROR LED is on, 

perform a Basic Calibration followed by a Field Calibration. Turn the power off 

for 5 seconds. Turn power on and check if the ERROR LED is on. If the LED 

is on, contact the factory.

EMC INSTALLATION GUIDELINES

Although Red Lion Controls Products are designed with a high degree of 

immunity to Electromagnetic Interference (EMI), proper installation and wiring 

methods must be followed to ensure compatibility in each application. The type 

of the electrical noise, source or coupling method into a unit may be different 

for various installations. Cable length, routing, and shield termination are very 

important and can mean the difference between a successful or troublesome 

installation. Listed are some EMI guidelines for a successful installation in an 

industrial environment.

1. A unit should be mounted in a metal enclosure, which is properly connected 

to protective earth.

2. Use shielded cables for all Signal and Control inputs. The shield connection 

should be made as short as possible. The connection point for the shield 

depends somewhat upon the application. Listed below are the recommended 

methods of connecting the shield, in order of their effectiveness.

a. Connect the shield to earth ground (protective earth) at one end where the 

unit is mounted.

b. Connect the shield to earth ground at both ends of the cable, usually when 

the noise source frequency is over 1 MHz.

3. Never run Signal or Control cables in the same conduit or raceway with AC 

power lines, conductors, feeding motors, solenoids, SCR controls, and 

heaters, etc. The cables should be run through metal conduit that is properly 

grounded. This is especially useful in applications where cable runs are long 

and portable two-way radios are used in close proximity or if the installation 

is near a commercial radio transmitter. Also, Signal or Control cables within 

an enclosure should be routed as far away as possible from contactors, 

control relays, transformers, and other noisy components. 

4. Long cable runs are more susceptible to EMI pickup than short cable runs.

5. In extremely high EMI environments, the use of external EMI suppression 

devices such as Ferrite Suppression Cores for signal and control cables is 

effective. The following EMI suppression devices (or equivalent) are 

recommended:

Fair-Rite part number 0443167251 (RLC part number FCOR0000)

Line Filters for input power cables:

Schaffner # FN2010-1/07 (Red Lion Controls # LFIL0000)

6. To protect relay contacts that control inductive loads and to minimize radiated 

and conducted noise (EMI), some type of contact protection network is 

normally installed across the load, the contacts or both. The most effective 

location is across the load.

a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide 

varistor (MOV) across an AC inductive load is very effective at reducing 

EMI and increasing relay contact life.

b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor 

switch, care must be taken not to exceed the breakdown voltage of the 

transistor when the load is switched. One of the most effective ways is to 

place a diode across the inductive load. Most RLC products with solid 

state outputs have internal zener diode protection. However external diode 

protection at the load is always a good design practice to limit EMI. 

Although the use of a snubber or varistor could be used.

RLC part numbers: Snubber: SNUB0000

   

Varistor: ILS11500 or ILS23000

7. Care should be taken when connecting input and output devices to the 

instrument. When a separate input and output common is provided, they 

should not be mixed. Therefore a sensor common should NOT be connected 

to an output common. This would cause EMI on the sensitive input common, 

which could affect the instrument’s operation.
Visit RLC’s web site at http://www.redlion.net/Support/InstallationConsiderations.

html for more information on EMI guidelines, Safety and CE issues as they 

relate to Red Lion Controls products.

ANALOG

OUTPUT

CIRCUITRY

1

3

CIRCUITRY

CONTROL

PWM

POWER

SUPPLY

22V

3V

CIRCUITRY

PROCESS

CONVERTER

A/D

8

7

1.7V

3V

22M

TC

+
-

CURRENT
OUTPUT

12

10

1.7V

4V

POWER

DC

6

4

+

+

-

-

VOLTAGE
OUTPUT

BLOCK DIAGRAM

TC 

(INPUT) RANGE

DIP SWITCH 

TYPE RANGE 

 

6  7  8  9 10

TEMPERATURE 

& mV RANGE

RANGE 

ACCURACY

WIRE COLOR 

 

  ANSI       BS1843

0

1  1  1  0  0

-9 to 6 mV

±

 0.0113 mV

N/A

Yellow (+) 

Blue (-)

1

1  1  1  0  1

-9 to 22 mV

±

 0.0233 mV

Brown (+) 

Blue (-)

White (+) 

Blue (-)

2

1  1  1  1  0

-9 to 63 mV

±

 0.0540 mV

Brown (+) 

Blue (-)

mV

3

1  1  1  1  1

-9 to 77 mV

±

 0.0645 mV

N/A

0

0  0  0  0  0 -136 to 111°C

±

 0.19°C

1

0  0  0  0  1

69 to 575°C

±

 0.38°C

2

0  0  0  1  0 338 to 800°C

±

 0.35°C

J

3

0  0  0  1  1 -149 to 862°C

±

 0.76°C

White (+) 

Red (-)

0

0  0  1  0  0 -200 to 541°C

±

 0.56°C

1

0  0  1  0  1 427 to 1132°C

±

 0.53°C

2

0  0  1  1  0 648 to 1372°C

±

 0.54°C

K

3

0  0  1  1  1 -192 to 1372°C

±

 1.17°C

Yellow (+) 

Red (-)

0

0  1  0  0  0 -225 to 149°C

±

 0.28°C

1

0  1  0  0  1

74 to 326°C

±

 0.19°C

2

0  1  0  1  0

68 to 400°C

±

 0.25°C

T

3

0  1  0  1  1 -200 to 400°C

±

 0.45°C

Blue (+) 

Red (-)

0

0  1  1  0  0 -111 to 311°C

±

 0.32°C

1

0  1  1  0  1 276 to 609°C

±

 0.25°C

2

0  1  1  1  0 377 to 1000°C

±

 0.47°C

E

3

0  1  1  1  1 -114 to 1000°C

±

 0.84°C

Violet (+) 

Red (-)

Ice Point

Total Error

( ±0.19°C +

±0.25°C

+ ±0.50°C  ) =

±0.94°C

Accuracy Example:

  Type “J” Range “0”

   -136°C to 111°C

 

Note: DIP switch settings 

ON = 1  OFF = 0

Conformity

Range

Содержание ITMA

Страница 1: ...ment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired SPECIFICATIONS 1 POWER 9 to 32 VDC 1 75 W The power supply must have 300 mA for 200...

Страница 2: ...rols and heaters etc The cables should be run through metal conduit that is properly grounded This is especially useful in applications where cable runs are long and portable two way radios are used i...

Страница 3: ...e case and cut the wire jumper The jumper is located to the left side of the board as shown in the drawing POWER Connect DC power to terminals 10 and 12 observing proper polarity Be certain DC power i...

Страница 4: ...en turn on power and the previous settings will be loaded Field Calibration with a Thermocouple Calibrator 1 1 Enable the Ice Point Compensation on the Thermocouple Calibrator and set it to the Thermo...

Страница 5: ...Output increases to 0 8 mA 3 5 mA or 0 4 V nominal or more 4 19 Perform a Field Calibration See Section 1 0 1 2 3 4 5 6 7 9 8 10 ON 1 2 3 4 5 6 7 9 8 10 ON 1 2 3 4 5 6 7 9 8 10 ON 1 2 3 4 5 6 7 9 8 1...

Страница 6: ...S POWER SUPPLY 24VDC COMM MASTER CONTROL ROOM G Rail Installation To install the ITMA on a G style DIN rail angle the module so that the upper groove of the foot catches under the lip of the top rail...

Страница 7: ...7 This page intentionally left blank...

Страница 8: ...Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any p...

Отзывы: