background image

Series TY-FRB – 5.6 and 8.0 K-factor 

Extended Coverage Horizontal Sidewall Sprinklers 

Quick and Standard Response (Light Hazard)

Page 1 of 8 

AUGUST 2018 

TFP296

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

TYCO Series TY-FRB 5.6 and 8.0 

K-factor Extended Coverage Hori-

zontal Sidewall Sprinklers Quick and 

Standard Response (Light Hazard) are 

decorative 3 mm glass bulb type spray 

sprinklers designed for use in hydrau-

lically calculated sprinkler systems in 

light hazard, commercial occupancies 

such as churches, restaurant seating 

areas, hotels, educational facilities, 

offices, etc. With their coverage up 

to 16 ft (4,9 m) wide by 24 ft (7,3 m) 

long, they are designed for installation 

along a wall or the side of a beam and 

just beneath a smooth ceiling. Hori-

zontal sidewall (HSW) sprinklers are 

commonly used instead of pendent or 

upright sprinklers due to aesthetics or 

building construction considerations, 

where piping across the ceiling is not 

desirable.
The fast response thermal sensitivity 

rating of the Series TY-FRB, 3 mm bulb 

type sprinklers provides for a quick 

response extended coverage (QREC) 

rating for many of the coverage areas 

detailed in Tables B and C.
The recessed version of the Series 

TY-FRB Extended Coverage Horizontal 

Sidewall Sprinkler utilizes either a two-

piece Style 10 (1/2 in. NPT) or Style 

40 (3/4 in. NPT) Recessed Escutch-

eon with 1/2 in. (12,7 mm) of recessed 

adjustment or up to 3/4 in. (19,1 mm) 

of total adjustment from the flush side-

wall position, or a two-piece Style 20 

(1/2 in. NPT) or Style 30 (3/4 in. NPT) 

Recessed Escutcheon with 1/4 in. (6,4 

mm) of recessed adjustment or up to 

1/2 in. (12,7 mm) of total adjustment 

from the flush sidewall position. The 

adjustment provided by the Recessed 

Escutcheon reduces the accuracy to 

which the fixed pipe lengths to the 

sprinklers must be cut.
Corrosion resistant coatings, where 

applicable, are utilized to extend the life 

of copper alloy sprinklers beyond that 

which would otherwise be obtained 

when exposed to corrosive atmo-

spheres. Although corrosion resistant 

coated sprinklers have passed the 

standard corrosion tests of the appli-

cable approval agencies, the testing is 

not representative of all possible cor-

rosive atmospheres. Consequently, 

it is recommended that the end user 

be consulted with respect to the suit-

ability of these coatings for any given 

corrosive environment. The effects of 

ambient temperature, concentration of 

chemicals, and gas/chemical velocity, 

should be considered, as a minimum, 

along with the corrosive nature of the 

chemical to which the sprinklers will be 

exposed.

NOTICE

The Series TY-FRB Sprinklers 

described herein must be installed 

and maintained in compliance with this 

document, as well as with the applica-

ble standards of the National Fire Pro-

tection Association (NFPA), in addition 

to the standards of any other authori-

ties having jurisdiction. Failure to do so 

may impair the performance of these 

devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Numbers (SINs)

TY3332

. . .

EC HSW, 5.6K, 1/2 in. NPT

TY4332

. . .

EC HSW, 8.0K, 3/4 in. NPT

Содержание tyco TY-FRB Series

Страница 1: ...r utilizes either a two piece Style 10 1 2 in NPT or Style 40 3 4 in NPT Recessed Escutch eon with 1 2 in 12 7 mm of recessed adjustment or up to 3 4 in 19 1 mm of total adjustment from the flush side wall position or a two piece Style 20 1 2 in NPT or Style 30 3 4 in NPT Recessed Escutcheon with 1 4 in 6 4 mm of recessed adjustment or up to 1 2 in 12 7 mm of total adjustment from the flush sidewa...

Страница 2: ...s as outlined in the appliable installation standard recognized by the Approval Agency e g UL recognizes NFPA 13 and FM recognize the FM Loss Preven tion Data Sheets Only the Style 10 20 30 or 40 Recessed Escutcheon as applicable is to be used for recessed installations 2 5 4 6 1 3 WRENCH FLATS 1 1 2 38 1 mm 2 3 16 55 6 mm 7 16 11 1 mm NOMINAL MAKE IN 1 9 16 39 7 mm DEFLECTOR HAT 1 2 NPT 7 7 16 11...

Страница 3: ...tual Research Corporation FM per Table D 4 Approved by the City of New York under MEA 354 01 E 5 Where Polyester Coated Sprinklers are noted to be UL and C UL Listed the sprinklers are UL and C UL Listed corrosion resistant sprinklers a Installed with Style 10 1 2 in NPT or Style 40 3 4 in NPT 3 4 in Total Adjustment Recessed Escutcheon as applicable b Installed with Style 20 1 2 in NPT or Style 3...

Страница 4: ...4 0 5 Quick 16 x 22 4 9 x 6 7 36 136 20 3 1 59 4 to 12 100 to 300 135 10 3 1 13 4 0 5 Quick 16 x 24 4 9 x 7 3 39 148 23 8 1 64 4 to 6 100 to 150 135 10 3 1 13 4 0 5 Quick 16 x 24 4 9 x 7 3 40 151 25 0 1 72 4 to 12 100 to 300 135 10 3 1 13 4 0 5 Standard 16 x 20 4 9 x 6 1 32 121 16 0 1 10 4 to 6 100 to 150 155 10 3 1 13 4 0 5 Standard 16 x 20 4 9 x 6 1 33 125 17 0 1 17 4 to 12 100 to 300 155 10 3 1...

Страница 5: ...6 20 1 38 4 to 12 100 to 300 135 155 10 3 1 Quick 16 x 20 4 9 x 6 1 40 151 25 1 72 4 to 12 100 to 300 135 155 10 3 1 Quick 16 x 22 4 9 x 6 7 44 167 30 2 06 4 to 12 100 to 300 135 155 10 3 1 Quick 16 x 24 4 9 x 6 7 48 182 36 2 48 4 to 12 100 to 300 135 155 10 3 1 Standard 16 x 16 4 9 x 4 9 32 121 16 1 10 4 to 12 100 to 300 175 10 3 1 Standard 16 x 18 4 9 x 5 5 36 136 20 1 38 4 to 12 100 to 300 175 ...

Страница 6: ...6 and 8 0 K factor Extended Coverage Horizon tal Sidewall Sprinklers Quick and Stan dard Response Light Hazard must be maintained and serviced in accordance with this section Before closing a fire protection system main control valve for maintenance work on the fire pro tection system that it controls per mission to shut down the affected fire protection system must be obtained from the proper aut...

Страница 7: ...m 1 1 4 31 8 mm CLOSURE 1 4 6 4 mm 1 2 12 7 mm MOUNTING PLATE MOUNTING SURFACE FACE OF SPRINKLER FITTING 2 1 4 DIA 57 2 mm 2 7 8 DIA 73 0 mm SERIES TY FRB EC 1 8 3 2 mm 1 2 1 8 12 7 3 2 mm FIGURE 5 SERIES TY FRB RECESSED EC SIDEWALL SPRINKLER ASSEMBLY WITH TWO PIECE 3 4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 5 6 K FACOTR 1 2 INCH NPT FIGURE 6 SERIES TY FRB RECESSED EC SIDEWALL SPRINKLE...

Страница 8: ...rt Number P N Sprinkler Assembly with NPT Thread Connections Specify Series TY FRB specify SIN Extended Coverage Horizontal Side wall Sprinkler K specify specify temperature rating specify finish P N specify from Table E Recessed Escutcheon Specify Style 10 20 30 or 40 Recessed Escutcheon with specify finish P N specify Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify W Type 6 Sprinkl...

Отзывы: