Overview of Error Blink Codes
•
241
Auxiliary
Commands
WAGO-I/O-SYSTEM 750
I/O Modules
Address
Configuration
variable
Dec. Hex.
Data
type
Default Range
Description
Speed
40
0x28
INT16
10
1 ... 25000
Default speed
Speed_Limit
42
0x2A INT16
25000
1 ... 25000
Default maximum speed; the drive is
switched off if this speed is exceeded
SetupSpeed
44
0x2C
INT16
100
1 ... 25000
Default setup speed; the current moving
speed is used when this parameter is 0.
Acceleration_
Stop_Fast
46
0x2E
INT16
1000
0 ... 32767
Default acceleration for STOP mode;
the current acceleration is used when
this parameter is 0.
Acceleration_
RampUp
48
0x30
INT16
10
0 ... 32767
Default acceleration for acceleration
phase
Acceleration_
RampDown
50
0x32
INT16
10
0 ... 32767
Default acceleration for deceleration
phase
Acceleration_
RampUp_Param
52 0x34 INT32 300 0
...
16777216
Default acceleration time or acceleration
path
Acceleration_
RampDown_
Param
56 0x38 INT32 300 0
...
16777216
Default deceleration time or deceleration
path