Overview of Error Blink Codes
Auxiliary
Commands
WAGO-I/O-SYSTEM
750
I/O
Modules
Bit number
Default
Name
Dec.
Hex.
Type
Target/Source Bit no.
Description
Acc_Range_
Sel_0
198 0xC6 DST/
SRC
KBUS_CTRL2
_0
0x48
Configuration factor Acceleration.
These two bits are used to set the
ACC_Multiplier factor for acceleration.
These values are accepted only when Enable
is set to 0.
Acc_
Range_
Sel_0
Acc_
Range_
Sel_1
0 0 The
factor
Acc_Multiplier is
loaded with the
parameter Acc_Fact
from the current
configuration data set
(*).
0
1
Acc_Multiplier = 80
T = 760 ms
1
0
Acc_Multiplier = 800
T = 76 ms
1
1
Acc_Multiplier = 8000
T = 7.6 ms
Acc_Range_
Sel_1
199 0xC7 DST/
SRC
KBUS_CTRL2
_1
0x49
(*) If the parameter Acc_Fact in the
configuration data set has been assigned a
value of zero, the factor is set to
Acc_Multiplier = 8 (T = 7.6s) for
Acc_Range_Sel_0 = 0 and
Acc_Range_Sel_1 = 0.
Set_Actual_
POS
200 0xC8 DST/
SRC
KBUS_CTRL3
_0
0x50
The actual value is set to the reference position
(configuration parameter Reference_Offset) on
a rising edge from the bit Set_Actual_POS.
This function cannot be performed while a
positioning run is ongoing.
201
0xC9
202
0xCA
203
0xCB
204
0xCC
205
0xCD
206
0xCE
207
0xCF
LED E
208 0xD0 DST/
SRC
Busy 0x09
LED
E
LED F
209 0xD1 DST/
SRC
M_Program_A
CK
0x1B LED
F