Overview of Error Blink Codes
•
221
Auxiliary
Commands
WAGO-I/O-SYSTEM 750
I/O Modules
Bit number
Default
Name
Dec.
Hex.
Type
Target/Source Bit no.
Description
Set when reference run has been successfully
concluded
0: This bit is at 0 when the module is
activated. Additionally, it is also set to 0
when the reference run is started.
Reference_
OK
13 0x0D SRC KBUS_ST2_5
0x8D
1: The reference point has been successfully
located in the reference run mode.
Setpoints from Mode 2.2 saved.
This bit is set when the setpoint save mode has
been requested with PreCalc and precalculation
of a movement has been successfully
completed.
0: Precalculation not yet performed.
PreCalc_Ack 14 0x0E SRC KBUS_ST2_6 0x8E
1: Precalculation
performed.
Drive error status.
An error can be acknowledged using
Error_Quit.
0: No error present for the drive.
Error 15
0x0F
SRC
KBUS_ST2_7
OUT2
0x8F
0xA1
1: Error present for the drive.
Ready for operation
0: The module is not ready for operation.
Either a corresponding request is present
via Enable, or an error has resulted in
cancellation of Ready. When the bit
switches from 1 to 0 the output stage is
deactivated, or the output frequency is set
to 0.
Ready 16
0x10
SRC
KBUS_ST1_0
0x80
1: Readiness for operation has been
requested via Enable and no error is
present.
Drive Stop inverted
0: The bit Stop1_N or Stop2_N is set to 0.
The motor has stopped (StandStill is set to
1). Start cannot be used to start-up the
unit.
Stop_N_AC
K
17 0x11 SRC KBUS_ST1_1
LED G
0x81
0xD2
1: The bits Stop1_N and Stop2_N are both
set to 1, or the drive is braking the unit.