232 •
Overview of Error Blink Codes
Auxiliary
Commands
WAGO-I/O-SYSTEM
750
I/O
Modules
Bit number
Default
Name
Dec.
Hex.
Type
Target/Source Bit no.
Description
Move in positive direction.
This bit is required for the Jog mode. When
this mode has been selected, the drive is
controlled using these bits.
In the Reference run mode this bit defines that
the reference switch be searched for in a
positive direction.
0:
Drive not to move in a positive direction.
Direction_
Pos
186 0xBA DST/
SRC
KBUS_CTRL3
_2
0x52
1:
Drive should move in a positive
direction. The drive is deactivated when
the bit Direction_Neg is set at the same
time.
Move in negative direction.
This bit is required for the Jog mode. When
this mode has been selected, the drive is
controlled using these bits.
In the Reference run mode this bit defines that
the reference switch be searched for in a
negative direction.
0:
Drive not to move in a negative
direction.
Direction_
Neg
187 0xBB DST/
SRC
KBUS_CTRL3
_3
0x53
1:
Drive should move in a negative
direction. The drive is deactivated when
the bit Direction_Pos is set at the same
time.
Reference input
Input 2 is set to this bit in the standard
configuration.
0:
The reference switch is not actuated.
Set_
Reference
188 0xBC DST/
SRC
Input2 0x31
1:
The reference switch is actuated.