Overview of Error Blink Codes
•
219
Auxiliary
Commands
WAGO-I/O-SYSTEM 750
I/O Modules
Bit number
Default
Name
Dec.
Hex.
Type
Target/Source Bit no.
Description
I/O module communication active
0: No I/O module communication for more
than 100 ms
KBUS_
Active
6 0x06
SRC
-
-
1: I/O module communication present
7
0x07
The significance of this bit depends on the
selected operating mode.
Step positioning:
0: The defined position has not been
reached.
1: The defined position has been reached.
Move program:
0: The Move program was not terminated by
the PROG_STOP drive command.
1: The Move program was terminated by the
PROG_STOP drive command.
Reference run:
0: The bit is set to 0 when the reference run
is started.
1: Not
used.
Jog Mode:
0: The bit is set to 0 when the Jog mode is
started.
1: Not
used.
Mailbox mode:
0: Moving to a new position.
On_Target 8 0x08 SRC KBUS_ST2_0
OUT1
0x88
0xA0
1: The current command has been
successfully concluded.