![WAGO I/O SYSTEM 750 750-671 Скачать руководство пользователя страница 182](http://html1.mh-extra.com/html/wago/i-o-system-750-750-671/i-o-system-750-750-671_manual_3328297182.webp)
182 •
Reference Commands for Move Mode
Setpoint
commands
WAGO-I/O-SYSTEM
750
I/O
Modules
3.2.4.1.18
SET_ACTUALPOSITON (0x2E)
The current position is set to the transferred value. The logical zero point is
modified accordingly for this.
The position is given as a 24-bit value, including sign.
Request
Byte 2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
MB0
0x40
MB1 T
-
MB2
0x2E
MB3 Position
(LSB)
MB4 Position
MB5 Position
(MSB)
Response
Byte 2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
MB0
0x40
MB1 T
Return
Code
MB2
0x2E
MB3 Reserved
MB4 Reserved
MB5 Reserved