INSTRUCTION MANUAL

THERMOCOUPLE INPUT MODULE, 4 points

(L

ON

W

ORKS

)

MODEL

R7L-TS4

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Thermocouple input module (body + 4 CJC sensors) ........(1)
NeuronID label ....................................................................(2)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.
LNS Plug-in Software (model: R7LPLG) is usable to set up 
Functional Blocks.  For detailed information, refer to the 
R7PLG Users Manual.  The R7LPLG is downloadable at M-
System’s web site: http://www.m-system.co.jp

POINTS OF CAUTION

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

    24V AC rating: 24V ±10%, 50/60 Hz, approx. 85mA
    24V DC rating: 24V ±10%, approx. 50mA

 

GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and input signal for safety.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

Содержание R7L-TS4

Страница 1: ...www m system co jp POINTS OF CAUTION POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V AC rating 24V 10 50 60 Hz approx 85mA 24V DC rating 24V 10 approx 50mA GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and input signal for safety ENVIRONMENT Indoor use When heavy...

Страница 2: ... stopped OFF Normal state INDICATOR LED Used to show network variable status assigned to fbLED ON LED ON OFF LED OFF SERVICE SWITCH Used to identify the node in LONWORKS network configura tion RESET SWITCH Used to reset the Neuron Chip Press the switch behind the front cover to reset Control functions are halted while completing resetting and restarting Confirm no danger before conducting resettin...

Страница 3: ...TERMINALS for LONWORKS POWER 18 M3 SCREW TERMINALS for INPUT 6 24 6 24 30 1 18 5 20 DIN RAIL 35mm wide 54 2 13 17 66 CONNECTION DIAGRAM 4 7 6 3 2 5 1 V U FG NET2 NET2 NET1 NET1 Input Connection Example INn INn CJn CJn T C CJC SENSOR 10 IN0 11 IN0 1 CJ0 2 CJ0 IN1 IN1 CJ1 CJ1 IN2 IN2 CJ2 CJ2 IN3 IN3 CJ3 CJ3 INPUT 0 12 13 3 4 INPUT 1 15 16 6 7 INPUT 2 17 18 8 9 INPUT 3 INn INn Short CJC SENSOR CJn CJ...

Страница 4: ...ONNECTION HOST PC LONWORKS R7L LONWORKS R7L LONWORKS Terminator WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Applicable wire size 0 25 to 1 65 mm2 AWG 22 to 16 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Nichifu Co Ltd 6 24 max 3 3 13 max mm inch ...

Страница 5: ...ng Maximum sending time per fb Minimum sending time per fb Set Tag No name Indicate Model No and Version Indicate Serial No NodeObject Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviRequest SNVT_obj_request For use with LonMaker and other tools nvoStatus SNVT_obj_status For use with LonMaker and other tools nvoFileDirectory SNVT_add...

Страница 6: ...0 0 0 Maximum time interval to send network variables per fb Power supply must be reset when this configuration prop erty is changed Network variables are sent out in the specified intervals even when there is no change in the value No sending when a value less than 10 0 is set Invalid property when the assigned fb has no network vari ables to be sent to the network SCPTminSendTime Number of fb SN...

Страница 7: ...CNTOut Set the maximum count Set the value when fbCNT is reset fbCNT SCPTdirection nviCNTIn SCPTinvrtOut nviCNTCtrl SCPTpwrUpState nvoCNTOut SCPTnvType SCPTmaxRnge SCPTsetpoint Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviCNTIn SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Counted object nviCNTCtrl SNVT_switch 0 0 0 100 0 1 Invalid 0 0 ...

Страница 8: ...1 Count always reset to 0 Bit 5 8 through 15 Invalid Minimum input pulse width 500 ms for nviCNTIn 50 ms for the input terminals DO NOT connect a network variable to nviCNTIn when one of the input terminals other than nviCNTIn is assigned as the counted object ON time per 1 second increments SCPTinvrtOut nviCNTIn SNVT_lev_disc ST_OFF ST_ON ST_OFF Count logic at nviCNTIn ST_OFF Count with nvoCNTIn ...

Страница 9: ... and 100 setpoints Zero adjustment Span adjustment fbTS SCPTsceneNmbr nvoTSVal SCPTnvType SCPTminDeltaTemp SCPToffset SCPTdefScale SCPTsetpoint nvoTSPVal SCPToffset SCPTgain Network Variables Configuration Properties Thermocouple input Input 0 Input 1 Input 2 Input 3 nv 60 nv 63 nv 64 nv 67 Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nvoTSVal SNVT_temp 274 0 6279 5 0 0 SNVT_...

Страница 10: ...set 1 SCPToffset 0 SCPTdefScale nvoTSVal SNVT_lev_percent 80 000 120 000 0 0 Gain applied to SCPToffset 0 SCPTsetpoint 0 nvoTSVal Same as nvoTSVal nvoTSVal lower range temperature SCPTsetpoint 0 SCPTsetpoint 1 SCPTsetpoint 1 nvoTSVal Same as nvoTSVal nvoTSVal upper range temperature SCPTsetpoint 0 SCPTsetpoint 1 SCPToffset nvoTSPVal SNVT_lev_percent 163 840 163 835 0 0 nvoTSPVal zero offset adjust...

Страница 11: ...ariable type 0 and 100 setpoints Network variable type 0 and 100 setpoints nviCVIn SCPTnumDigits SCPTnvType SCPTsetpoint nvoCVOut SCPTnvType SCPTsetpoint Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviCVIn SNVT_lev_percent 163 840 163 835 0 0 SNVT_temp 274 0 6279 5 0 0 SNVT_temp_p 273 17 327 66 0 0 SNVT_count_32 0 999 999 999 0 Inpu...

Страница 12: ...that of the source when using 60 63 SCPTnvType nviCVIn SNVT_nv_type SNVT_temp Indicates nviCVIn type For use with LonMaker and other tools SCPTnvType nvoCVOut SNVT_nv_type SNVT_temp Indicates nvoCVOut type For use with LonMaker and other tools SCPTsetpoint 0 nviCVIn Same as nviCVIn Scaling setting Output SCPTsetpoint 0 nvoCVOut is provided with the input SCPTsetpoint 0 nviCVIn Output SCPTsetpoint ...

Страница 13: ...S nviARMIn SNVT_lev_percent 163 840 163 835 0 0 SNVT_temp 274 0 6279 5 0 0 SNVT_temp_p 273 17 327 66 0 0 SNVT_count_32 0 999 999 999 0 Inputs the value to be compared to the alarm setpoint nvoARM1 SNVT_switch 0 0 0 100 0 1 0 0 1 nviARMIn alarm 1 HH 100 0 1 with nviARMIn SCPTsetpoint 0 Reset to 0 0 0 from 100 0 1 with nviARMIn SCPTsetpoint 0 SCP Toffset nvoARM2 SNVT_switch 0 0 0 100 0 1 0 0 1 nviAR...

Страница 14: ...ARMIn SNVT_nv_type SNVT_lev_percent Indicates nviARMIn type For use with LonMaker and other tools SCPTsetpoint 0 nviARMIn SNVT_lev_percent 163 840 163 835 80 000 SNVT_temp 274 0 6279 5 80 0 SNVT_temp_p 273 17 327 66 80 00 SNVT_count_32 0 999 999 999 10 000 Alarm 1 nvoARM1 setpoint SCPTsetpoint 1 nviARMIn SNVT_lev_percent 163 840 163 835 60 000 SNVT_temp 274 0 6279 5 60 0 SNVT_temp_p 273 17 327 66 ...

Страница 15: ... nv 97 nviLEDIn01 SNVT_switch nv 98 nviLEDIn02 SNVT_switch nv 99 nviLEDIn03 SNVT_switch nv 112 nviLEDIn16 SNVT_switch Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviLEDState SNVT_state 0 or 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 The front LEDs 0 F turn on off according to the input Bit 0 through Bit 15 assigned to LED 0 through F respect...

Страница 16: ...riables Configuration Properties Extension discrete output Y0 Y2 Y4 Y6 Y8 YA YC YE Output nviDOEX1 status Y1 Y3 Y5 Y7 Y9 YB YD YF Output nviDOEX2 status nv 4 nv 11 nviDOEX1 SNVT_switch nv 12 nv 19 nviDOEX2 SNVT_switch Output Terminal v s fbDOEX Network Variables nviDOEX1 nviDOEX2 Assignments FUNCTIONAL BLOCK NETWORK VARIABLE OUTPUT TERMINAL fbDOEX 0 nviDOEX1 Y0 nviDOEX2 Y1 fbDOEX 1 nviDOEX1 Y2 nvi...

Страница 17: ...on or off Y1 Y3 Y5 Y7 Y9 YB YD YF of the extension module depending upon this input 100 0 1 ON Other OFF Configuration Properties CONFIGURATION PROPERTY NETWORK VARIABLE TYPE Range Default EXPLANATIONS SCPTdirection SNVT_state 0 or 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 1 Output held or not at power off 0 OFF at the power startup 1 Outputs the held status at the power startup Bit 0 Bit 2 through 15...

Страница 18: ...X8 XA XC XE X1 X3 X5 X7 X9 XB XD XF Normal Mode Status output at nvoDIEX1 Status output at nvoDIEX2 Combination Mode Refer to the table in the next page fbDIEX SCPTdirection nvoDIEX1 SCPTinvrtOut nvoDIEX2 SCPTinvrtOut Set operating mode Invert output Invert output Input Terminal v s fbDIEX Network Variables nvoDIEX1 nvoDIEX2 Assignments FUNCTIONAL BLOCK NETWORK VARIABLE INPUT TERMINAL fbDIEX 0 nvo...

Страница 19: ...4 X6 X8 XA XC XE X1 X3 X5 X7 X9 XB XD XF nvoDIEX1 nvoDIEX2 OFF OFF 0 0 0 OFF Invalid ON OFF 100 0 1 ON Invalid OFF ON 0 0 0 OFF 0 0 0 OFF ON ON 100 0 1 ON 100 0 1 ON nvoDIEX2 SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Configuration Properties CONFIGURATION PROPERTY NETWORK VARIABLE TYPE Range Default EXPLANATIONS SCPTdirection SNVT_state 0 or 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 0 Bit 1 fbDIEX opera...

Отзывы: