61
Viconics Technologies Inc.
www.viconics.com
|
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
028-0427-11
October 2018
3/9 Service View
UI16 binary
Airflow level
UI19 analog
UI17 binary
0 CFM
0 %
Zigb. sens. mot.
Zigb. PIR inst.
No motion
Off
Not activ.
Not activ.
Only for models with ZigBee
Pro communication module
SERVICE VIEW 3/9
PARAMETER DETAILS
Configuration parameters Default Value
Significance and Adjustments
UI16 binary
Read Only
Universal Input Configuration No. 1
Shows status of input.
Display Readings
: Activated or Not Activated
UI17 binary
Read Only
Universal Input Configuration No. 2
Shows status of input.
Display Readings
: Activated or Not Activated
UI19 analog
Read Only
Universal Input Configuration No. 3
Shows scaled percentage level of wired CO
2
sensor.
0% = 0ppm, 100% = 2000ppm
Display Readings
: 0-100%
Airflow level
Read Only
Airflow level
Shows the amount of air (in cubic feet/minute) that flows through a particular device.
Display Readings
: 0-100%
Zigb. PIR inst.
Read Only
ZigBee Passive Infrared Sensor Installed
Shows if ZigBee motion sensor is paired to a Room Controller or not.
NOTE:
This parameter is for ZigBee Motion Sensors only.
Display Readings:
Off or On
Zigb. sens. mot.
Read Only
ZigBee Sensor Motion
Shows if motion is detected by any of the wireless ZigBee motion sensors.
NOTE:
This parameter is for ZigBee Motion Sensors only.
Display Readings
: Motion or No Motion
Содержание VT8600 Series
Страница 3: ...SECTION 1 Introduction ...
Страница 6: ...HMI Display and Set up ...
Страница 10: ...SECTION 2 Customized Screens ...
Страница 17: ...Network Screens ...
Страница 25: ...Configuration Screens ...
Страница 48: ...Setpoints Screens ...
Страница 53: ...Display Screens ...
Страница 58: ...Service View Screens ...
Страница 68: ...Test Outputs Screens ...
Страница 71: ...Language Selection Screens ...
Страница 73: ...Schedule Screens ...
Страница 78: ...ADR Screens ...
Страница 81: ...Wireless Screens ...
Страница 92: ...LUA Screens ...
Страница 95: ...SECTION 3 Appendix ...