Permit timeout
Default value:
0
Read Only
Permit Join Timeout
Allows devices to join the Coordinator Room Controller for 180 minutes from the
moment it is set to ON. Once the timer elapses, no devices will be able to join the
network.
NOTE:
Permit Join parameter must be set to ‘On’ to enable this feature.
Range
: 0 or 180 minutes
Paired devices
Default value:
0
Read Only
Paired ZigBee Devices
Shows the number of Zigbee devices currently paired with the Room Controller. A
maximum of 10 ZigBee Pro devices and 1 ZigBee Green Power device can be paired
with each Room Controller (total of 11 paired devices per Room Controller).
Display Readings:
0 to 11 devices