34
Viconics Technologies Inc.
www.viconics.com
|
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
028-0427-11
October 2018
Frost protec
Default value: Off
Frost Protection
Stops the ventilation of the rooftop unit when room temperature reaches 42°F (5.6°C)
and resumes automatically when room temperature exceeds 15°F (-9°C).
Off
: No room frost protection
On
: Room frost protection enabled in all system modes at 42°F (5.6°C).
Frost protection is enabled even if System mode is ‘Off’.
Choices
: Off or On
BO1 aux config
Default value:
NO
Binary Auxiliary Output Configuration
Output to directly follow the main Occupancy and Fan On commands.
1. NO: Occ or St-By = Contact Closed / Unoccupied = Contact Opened
2. NC: Occ or St-By = Contact Opened / Unoccupied = Contact Closed.
Choices
: NO or NC
Anti short cycle
Default value:
2 minutes
Anti Short Cycle Time
Minimum On time and minimum Off time of operation time for stages.
IMPORTANT:
anti-short cycling can be set to 0 minutes for equipment that possess
their own anti cycling timer. Do not use this value unless the equipment is equipped
with an internal timer. Failure to do so can damage the equipment.
Range
: 0 to 5 minutes
Min. sup. heat
Default value:
64°F (18°C)
Minimum Supply Heat
Controls the modulating heating output to maintain the supply air temperature setpoint
(min. sup. heat).
Apply if “Heat Stages” parameter is set to 0 (Analog Heat on UO11). In Occupied
or Override mode, the output will modulate to maintain a minimum Supply Air
temperature. Conditional to SAT sensor installed, System Mode = Heat or Auto and
OAT < SH Lockout.
Range:
50°F to 72°F (10°C to 22°C)
Содержание VT8600 Series
Страница 3: ...SECTION 1 Introduction ...
Страница 6: ...HMI Display and Set up ...
Страница 10: ...SECTION 2 Customized Screens ...
Страница 17: ...Network Screens ...
Страница 25: ...Configuration Screens ...
Страница 48: ...Setpoints Screens ...
Страница 53: ...Display Screens ...
Страница 58: ...Service View Screens ...
Страница 68: ...Test Outputs Screens ...
Страница 71: ...Language Selection Screens ...
Страница 73: ...Schedule Screens ...
Страница 78: ...ADR Screens ...
Страница 81: ...Wireless Screens ...
Страница 92: ...LUA Screens ...
Страница 95: ...SECTION 3 Appendix ...