Shed offset
Default value:
4°F (2°C)
Load Shedding Offset
Used to change the effective setpoints in occupied, standby and unoccupied modes.
For example, when “Shed status” is On and Room Controller is in occupied mode, the
cooling setpoint is calculated as follows:
Occupied cooling setpoint = occupied cooling se Load shedding offset.
The heating setpoint is calculated as follows:
Occupied heating setpoint = occupied heating setpoint - Load shedding offset.
Choices
: 4°F to 10°F (2°C to 5.5°C)
Shed override
Default value:
Off
Read Only
Load Shedding Override
Displays whether the user disabled the ADR request by the utility company. When
the demand shed is applied, the user can override the ADR settings from its original
setpoints settings.
On
: Rejects or cancels shed load demand request from utility company (setpoints
remain the same).
Off
: Allows shed load demand request from utility company (setpoint will change
according to shed offset)
Display Readings
: On or Off
Содержание VT8600 Series
Страница 3: ...SECTION 1 Introduction ...
Страница 6: ...HMI Display and Set up ...
Страница 10: ...SECTION 2 Customized Screens ...
Страница 17: ...Network Screens ...
Страница 25: ...Configuration Screens ...
Страница 48: ...Setpoints Screens ...
Страница 53: ...Display Screens ...
Страница 58: ...Service View Screens ...
Страница 68: ...Test Outputs Screens ...
Страница 71: ...Language Selection Screens ...
Страница 73: ...Schedule Screens ...
Страница 78: ...ADR Screens ...
Страница 81: ...Wireless Screens ...
Страница 92: ...LUA Screens ...
Страница 95: ...SECTION 3 Appendix ...