52
Viconics Technologies Inc.
www.viconics.com
|
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
028-0427-11
October 2018
Min. cooling
Default value:
54°F (12°C)
Cooling Setpoint Limit
Maximum Occupied, Unoccupied, Standby and Override Cooling setpoint
adjustment.
Range:
54 to 100°F (12.0 to 37.5°C)
Supply air SP
Default value:
55°F (12°C)
Supply Air Setpoint
Free cooling supply air setpoint when economizer mode is enabled.
Range:
50 to 90°F (10.0 to 32.0°C)
Dehum. SP
Default value:
50%RH
Dehumidification Setpoint
Used only if dehumidification sequence is enabled.
Range
: 30 to 95% RH