26
Viconics Technologies Inc.
www.viconics.com
|
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
028-0427-11
October 2018
PARAMETER DETAILS
Configuration Parameters Default Value
Significance and Adjustments
UI16 config
Default value:
None
Universal Input Configuration No. 1
None
: No function will be associated with the input. Input can be used for remote
network monitoring.
Rem NSB
: Remote night setback (NSB) timer clock input. The scheduling gets set as
per the binary input and provides low cost setback operation via a dry contact
Motion NO and Motion NC
: Advanced PIR occupancy functions using a Normally
Open (NO) or Normally Closed (NC) remote PIR motion sensor.
Window
: Forces system to disable any current heating or cooling action by Room
Controller when window is open.
Fan lock
: When (G) Fan output is activated, if this input is not activated after 10
seconds, the Room Controller disables Heat and Cool outputs and display “Fan
Lock” alarm.
Open contact = No airflow alarm
Closed contact = Airflow present, normal operation
Choices:
None, Rem NSB, Motion NO, Motion NC, Window and Fan lock
1/11 Configuration
UI19 config
UI17 config
UI16 config
None
None
None
Smart recovery
Off
Setpoint func.
Attach SP
Mode button
Normal
CONFIGURATION 1/11
Содержание VT8600 Series
Страница 3: ...SECTION 1 Introduction ...
Страница 6: ...HMI Display and Set up ...
Страница 10: ...SECTION 2 Customized Screens ...
Страница 17: ...Network Screens ...
Страница 25: ...Configuration Screens ...
Страница 48: ...Setpoints Screens ...
Страница 53: ...Display Screens ...
Страница 58: ...Service View Screens ...
Страница 68: ...Test Outputs Screens ...
Страница 71: ...Language Selection Screens ...
Страница 73: ...Schedule Screens ...
Страница 78: ...ADR Screens ...
Страница 81: ...Wireless Screens ...
Страница 92: ...LUA Screens ...
Страница 95: ...SECTION 3 Appendix ...