SH lockout
Default value =
32°F (0°C)
Supply Heat Lockout
Disables heating operation if Outdoor Air Temperature (OAT) is higher than “SH
Lockout” temperature. The Outdoor Temperature value could be received from a
sensor connected directly to the Room Controller or via a BACnet front end (network).
Note:
valid only if “Heat Stages” parameter is set to 0 (Analog Heat on UO11).
Range:
-15°F to 120°F (-26°C to 49°C)
FA Range
Default value:
0 CFM
Fresh Air Range
Sets the upper limit (reading range) of the “airflow measuring station” (eg. for
0~1,000 CFM station, set “FA Range” to 1,000). If set to 0 CFM, this function is
disabled, and the fresh air damper control will be based on the “Min/Max CO
2
” and
“Econo Min/Max Pos” values if set to a value other than 0.
Do not change Econo Min/Max Pos if FA range is set to a value greater than 0.
Range:
0 to 20,000 CFM (±10 increments).
Содержание VT8600 Series
Страница 3: ...SECTION 1 Introduction ...
Страница 6: ...HMI Display and Set up ...
Страница 10: ...SECTION 2 Customized Screens ...
Страница 17: ...Network Screens ...
Страница 25: ...Configuration Screens ...
Страница 48: ...Setpoints Screens ...
Страница 53: ...Display Screens ...
Страница 58: ...Service View Screens ...
Страница 68: ...Test Outputs Screens ...
Страница 71: ...Language Selection Screens ...
Страница 73: ...Schedule Screens ...
Страница 78: ...ADR Screens ...
Страница 81: ...Wireless Screens ...
Страница 92: ...LUA Screens ...
Страница 95: ...SECTION 3 Appendix ...