20
Viconics Technologies Inc.
www.viconics.com
|
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
028-0427-11
October 2018
Channel
Default value:
10
ZigBee
Channel
The frequency or channel on which the ZigBee network transmits and receives data.
The channel of the Coordinator must match that of the routers to exchange data.
The default value of 10 is
NOT
a valid channel. The valid range of available channel is
from 11 to 25.
Using channels 15 and 25 is recommended.
Range
: 10 to 25
Network status
Read Only
ZigBee Network Status
Shows the current status of the ZigBee network.
No NWK
: ZigBee configured but no network joined
Joined
: ZigBee network joined
Online
: Communicating (Exchanging data)
Display Readings
: No NWK, Joined, Online
Permit join
Default value:
On
Permit Join
Changing this value to “Off” on the Coordinator prevents any new ZigBee devices
from joining the network.
Permit join can be On/Off when the Room Controller is a Coordinator, however the
parameter is read only when the Room Controller is a router. If not set to off manually
the Permit join will stay On for 3 hours.
Choices
: On or Off
Содержание VT8600 Series
Страница 3: ...SECTION 1 Introduction ...
Страница 6: ...HMI Display and Set up ...
Страница 10: ...SECTION 2 Customized Screens ...
Страница 17: ...Network Screens ...
Страница 25: ...Configuration Screens ...
Страница 48: ...Setpoints Screens ...
Страница 53: ...Display Screens ...
Страница 58: ...Service View Screens ...
Страница 68: ...Test Outputs Screens ...
Страница 71: ...Language Selection Screens ...
Страница 73: ...Schedule Screens ...
Страница 78: ...ADR Screens ...
Страница 81: ...Wireless Screens ...
Страница 92: ...LUA Screens ...
Страница 95: ...SECTION 3 Appendix ...