UI17 config
Default value:
None
Universal Input Configuration No. 2
None
: No function associated with input
Door Dry
: Room Controller goes to standby mode when door is opened then closed
followed by no presence detection for the next 10 seconds if the local PIR is used in
this application. The “Occupancy command” must be set to
“Local Occupancy” and “Occupancy Source” must be set to “Motion”.
Override
: A closed contact forces the Room Controller to go in occupied mode. An
open contact keeps the current occupancy mode.
Filter
: backlit flashing filter alarm shows on the Room Controller screen when input is
energized
Service
: backlit flashing Service alarm shows on Room Controller screen when input
is energized.
Choices
: None, Door Dry, Override, Filter and Service
UI19 config
Default value:
None
Universal Input Configuration No. 3
This input is used for a wired CO
2
sensor
None
: No function associated with input, however input can be used for remote
network monitoring
CO
2
:
Using the CO
2
level measured by a wired CO
2
sensor (0~2000 ppm = 0~10
Vdc), the Outside Air damper (Econo) will modulate between “Econo min pos” to
“Econo max pos” following the “Min CO
2
” and “Max CO
2
” setpoints.
Choices
: None or CO
2
Smart recovery
Default value:
Off
Enable Smart Recovery
Off
: No smart recovery. The occupied schedule time is the time at which the system
will restart.
On
: Smart recovery active. The occupied schedule time is the time at which the
desired occupied temperature will be attained. The Room Controller automatically
optimizes the equipment start time. In any case, the latest a system will restart is 10
minutes prior to the occupied period time.
Smart recovery is automatically disabled if BI16 is configured to remote NSB.
Choices
: Off or On
Setpoint func.
Default value:
Dual SP
Setpoint Function
Local setpoint settings to set the local setpoint interface for the User.
Dual SP
: “Minimum” Deadband, Heat and Cool Setpoints can be adjusted
independently.
Attach SP
: “Fixed” Deadband, Heat and Cool setpoints always follow each other,
separated by Deadband value (acts like a single setpoint).
Choices
: Dual SP or Attach SP
Содержание VT8600 Series
Страница 3: ...SECTION 1 Introduction ...
Страница 6: ...HMI Display and Set up ...
Страница 10: ...SECTION 2 Customized Screens ...
Страница 17: ...Network Screens ...
Страница 25: ...Configuration Screens ...
Страница 48: ...Setpoints Screens ...
Страница 53: ...Display Screens ...
Страница 58: ...Service View Screens ...
Страница 68: ...Test Outputs Screens ...
Страница 71: ...Language Selection Screens ...
Страница 73: ...Schedule Screens ...
Страница 78: ...ADR Screens ...
Страница 81: ...Wireless Screens ...
Страница 92: ...LUA Screens ...
Страница 95: ...SECTION 3 Appendix ...