2/2 Setpoints
Max. heating
Min. deadband
Default heat
1.5 °C
32.0 °C
12.0 °C
13.0 °C
22.0 °C
Min. cooling
Supply air SP
50 %RH
Dehum. SP
SETPOINTS 2/2
PARAMETER DETAILS
Configuration Parameters Default Value
Significance and Adjustments
Default heat
Default value:
72°F (22°C)
Default Heating Setpoint
Used for hospitality applications in stand-alone mode only to reset the occupied
setpoints when a new guest enters the room. When the Room Controller is in
unoccupied mode, any movement detected by a wired, wireless or local PIR sensor
changes the occupancy mode to occupied modes and uses the “Default Heating
Setpoint” as the new occupied setpoints.
NOTE
: This functionality is only valid when Stand-by mode = Offset and
“Setpoint Func” is set to “Attached”.
Range:
65 to 80°F (18.5 to 26.5°C)
Min. deadband
Default value:
3°F (1.5°C)
Minimum Deadband
Temperature offset between the Cooling and Heating setpoints to ensure that
Cooling setpoint is always warmer than the Heating setpoint
Cooling setpoint ≥ (Heating se Deadband)
Range:
2 to 5°F (1.0 to 2.5°C)
Max heating
Default value:
90°F (32°C)
Heating Setpoint Limit
Maximum Occupied, Unoccupied, Standby and Override Heating setpoints
maximum limit.
Range:
40 to 90°F (4.5 to 32.0°C)
Содержание VT8600 Series
Страница 3: ...SECTION 1 Introduction ...
Страница 6: ...HMI Display and Set up ...
Страница 10: ...SECTION 2 Customized Screens ...
Страница 17: ...Network Screens ...
Страница 25: ...Configuration Screens ...
Страница 48: ...Setpoints Screens ...
Страница 53: ...Display Screens ...
Страница 58: ...Service View Screens ...
Страница 68: ...Test Outputs Screens ...
Страница 71: ...Language Selection Screens ...
Страница 73: ...Schedule Screens ...
Страница 78: ...ADR Screens ...
Страница 81: ...Wireless Screens ...
Страница 92: ...LUA Screens ...
Страница 95: ...SECTION 3 Appendix ...