Heat stages
Default value:
2 stages
Number of Heating Stages
Sets number of Heating Stages applicable to 2 stage models only.
0 Stages:
Only (UO11) modulating 0-10Vdc output is used for Heating. W1 & W2 are
disabled.
1 Stage:
Only W1 (BO8) terminal is used. W2 is disabled.
2 Stages
: Both W1 (BO8) and W2 (UO9) terminals are used in sequence.
Choices:
0, 1 or 2 stages
Cool stages
Default value:
2 stages
Number of Cooling Stages
Sets number of Cooling Stages.
1 Stage:
Only Y1 (BO3) terminal is used. Y2 is disabled.
2 Stages:
Both Y1 (BO3) and Y2 (BO2) terminals are used in sequence.
Choices:
1 or 2 stages
Econo. config
Default value: Off
Economizer Configuration
Enables or disables the economizer functionality.
On:
Economizer activated
Off:
Economizer deactivated
Choices:
On or Off
Changeover SP
Default value:
55°F (13°C)
Changeover Setpoint
In Cooling mode, the outside air temperature value at which the cooling gets switched
over from mechanical (compressor) to free cooling (economizer).
Range
: 14°F to 70°F (-10°C to 21°C)
Содержание VT8600 Series
Страница 3: ...SECTION 1 Introduction ...
Страница 6: ...HMI Display and Set up ...
Страница 10: ...SECTION 2 Customized Screens ...
Страница 17: ...Network Screens ...
Страница 25: ...Configuration Screens ...
Страница 48: ...Setpoints Screens ...
Страница 53: ...Display Screens ...
Страница 58: ...Service View Screens ...
Страница 68: ...Test Outputs Screens ...
Страница 71: ...Language Selection Screens ...
Страница 73: ...Schedule Screens ...
Страница 78: ...ADR Screens ...
Страница 81: ...Wireless Screens ...
Страница 92: ...LUA Screens ...
Страница 95: ...SECTION 3 Appendix ...