Standby diff.
Default value:
4°F (2°C)
Standby Temperature Differential
When Standby mode is set to ‘offset’, standby setpoints are calculated as follows:
Standby cool
: Cool se Standby diff.
Standby heat
: Heat setpoint - Standby diff.
Range
: 1 to 5°F (0.5 to 2.5°C)
Power-up delay
Default value:
10 seconds
Power up Delay
On initial power up of the Room Controller there is a delay before any operation is
authorized (fan, cooling or heating). This can be used to sequence the start up of
multiple Room Controllers in one location.
Range
: 10 to 120 seconds
Occupancy src
Default value:
Motion
Occupancy Source
Motion
: occupancy status is received from a motion sensor from a wired, wireless or
local PIR sensor
Schedule:
occupancy status is determined by the schedule
Choices
: Motion or Schedule