1/2 Setpoints
Occ. cool
Standby cool
Unocc. cool
25.5 °C
24.0 °C
22.0 °C
20.5 °C
16.5 °C
26.5 °C
Occ. heat
Standby heat
Unocc. heat
PARAMETER DETAILS
Configuration Parameters Default Value
Significance and Adjustments
Unocc. cool
Default value:
80°F (27°C)
Unoccupied Cool Setpoint
Cooling Temperature setpoint used by the Room Controller when in
Unoccupied mode.
Range
: 54 to 100°F (12.0 to 37.5°C)
Standby cool
Default value:
78°F (25.5°C)
Standby Cooling Setpoint
Cooling Temperature setpoint used by the Room Controller when in
Standby mode.
Range:
54 to 100°F (12.0 to 37.5°C)
Occ. cool
Default value:
75°F (24°C)
Occupied Cool Setpoint
Cooling Temperature setpoint used by the Room Controller when in
Occupied or Override mode.
Range:
54 to 100°F (12.0 to 37.5°C)
Occ. heat
Default value:
72°F (22°C)
Occupied Heating Setpoint
Heating Temperature setpoint used by the Room Controller when in
Occupied mode.
Range:
40 to 90°F (4.5 to 32.0°C)
SETPOINTS 1/2
Содержание VT8600 Series
Страница 3: ...SECTION 1 Introduction ...
Страница 6: ...HMI Display and Set up ...
Страница 10: ...SECTION 2 Customized Screens ...
Страница 17: ...Network Screens ...
Страница 25: ...Configuration Screens ...
Страница 48: ...Setpoints Screens ...
Страница 53: ...Display Screens ...
Страница 58: ...Service View Screens ...
Страница 68: ...Test Outputs Screens ...
Страница 71: ...Language Selection Screens ...
Страница 73: ...Schedule Screens ...
Страница 78: ...ADR Screens ...
Страница 81: ...Wireless Screens ...
Страница 92: ...LUA Screens ...
Страница 95: ...SECTION 3 Appendix ...