2/11 Configuration
Fan delay
On
On
Standby mode
Absolute
Standby diff.
2.0 °F
Fan cont. heat
Power-up delay
10 Sec.
Occupancy src
Motion
CONFIGURATION 2/11
PARAMETER DETAILS
Configuration Parameters Default Value
Significance and Adjustments
Fan cont. heat
Default value:
On
Fan Control in Heating Mode
On
: Room Controller always controls the fan (terminal G). Valid for On or Auto fan
mode.
Off:
Fan (terminal G), when heating stages (terminals W1 & W2) are solicited, will not
be energized. The fan is controlled by the equipment fan limit control. Valid only for
Auto fan mode. On fan mode leaves the fan always on.
For multi-stage models, fan control applies to W1 & W2.
Choices
: On or Off
Fan delay
Default value:
On
Fan Delay
On
: fan mode will leave the fan always on and extends fan operation by 60 seconds
after the call for heating or cooling ends. Valid only for Auto fan mode.
Off
: fan delay not operational
Choices
: On or Off
Standby mode
Default value: Absolute
Standby Mode Configuration
Standby setpoints used for control.
Absolute
: Standby entered values are used for standby mode.
Offset:
Occupied set/- Standby diff. used for standby mode.
Choices
: Absolute or Offset
Содержание VT8600 Series
Страница 3: ...SECTION 1 Introduction ...
Страница 6: ...HMI Display and Set up ...
Страница 10: ...SECTION 2 Customized Screens ...
Страница 17: ...Network Screens ...
Страница 25: ...Configuration Screens ...
Страница 48: ...Setpoints Screens ...
Страница 53: ...Display Screens ...
Страница 58: ...Service View Screens ...
Страница 68: ...Test Outputs Screens ...
Страница 71: ...Language Selection Screens ...
Страница 73: ...Schedule Screens ...
Страница 78: ...ADR Screens ...
Страница 81: ...Wireless Screens ...
Страница 92: ...LUA Screens ...
Страница 95: ...SECTION 3 Appendix ...