BACnet Network Settings
BACnet network screen shows when BACnet is selected in wired protocol parameter.
1/2 BACnet Network
Baud rate
Auto
Network units
SI
Network lang.
English
BACnet status
Offline
COM address
254
PARAMETER DETAILS
Configuration Parameters Default Value
Significance and Adjustments
Comm address
Default value:
254
Communication Address
Room Controller networking address.
Default value of 254 disables BACnet communication for the Room Controller.
Range
: 0 to 254
Network units
Default value:
SI
Measurement Units
Network units transmitted over the BACnet network.
NOTE:
Use the Temperature scale parameter to change the display units locally on
the Room Controller.
Imperial
: Network units shown as Imperial units.
SI
: Network units shown as International Metric units.
Choices
: Imperial or SI
Network lang
Default value:
English
Network Language
Network language/object names transmitted over network.
Choices
: English, French or Spanish
Baud rate
Default value:
Auto
BACnet Baud Rate
Leave the value at
Auto
unless instructed otherwise as this automatically detects
BACnet baud rate.
Choices
: Auto, 115200, 76800, 57600, 38400, 19200, and 9600
BACnet status
Read Only
BACnet Status
Read Only value shows if a BACnet Network is detected or not.
Display Readings
: Online or Offline
Содержание VT8600 Series
Страница 3: ...SECTION 1 Introduction ...
Страница 6: ...HMI Display and Set up ...
Страница 10: ...SECTION 2 Customized Screens ...
Страница 17: ...Network Screens ...
Страница 25: ...Configuration Screens ...
Страница 48: ...Setpoints Screens ...
Страница 53: ...Display Screens ...
Страница 58: ...Service View Screens ...
Страница 68: ...Test Outputs Screens ...
Страница 71: ...Language Selection Screens ...
Страница 73: ...Schedule Screens ...
Страница 78: ...ADR Screens ...
Страница 81: ...Wireless Screens ...
Страница 92: ...LUA Screens ...
Страница 95: ...SECTION 3 Appendix ...