5/11 Configuration
Heat stages
Prop. band
2
3.0
Econo. config
Off
Changeover SP
55 °F
Cool stages
2
Mech. cooling
Off
CONFIGURATION 5/11
PARAMETER DETAILS
Configuration Parameters Default Value
Significance and Adjustments
Prop. band
Default value:
3
Proportional Band Setting
Adjusts proportional band used by Room Controller PI control loop.
Note:
Default value of 3 gives satisfactory operation in most normal installation cases.
The use of a superior proportional band different than the factory value is normally
warranted in applications where Room Controller location is problematic and leads
to unwanted cycling of the unit. A typical example is a wall mounted Room Controller
installed between return and supply air feeds and is directly influenced by the supply
air stream of unit.
Range:
3 to 10
Value
Effective Proportional Band
Fahrenheit
Celsius
3
3
1.2
4
4
1.7
5
5
2.2
6
6
2.8
7
7
3.3
8
8
3.9
9
9
5.0
10
10
5.6
Содержание VT8600 Series
Страница 3: ...SECTION 1 Introduction ...
Страница 6: ...HMI Display and Set up ...
Страница 10: ...SECTION 2 Customized Screens ...
Страница 17: ...Network Screens ...
Страница 25: ...Configuration Screens ...
Страница 48: ...Setpoints Screens ...
Страница 53: ...Display Screens ...
Страница 58: ...Service View Screens ...
Страница 68: ...Test Outputs Screens ...
Страница 71: ...Language Selection Screens ...
Страница 73: ...Schedule Screens ...
Страница 78: ...ADR Screens ...
Страница 81: ...Wireless Screens ...
Страница 92: ...LUA Screens ...
Страница 95: ...SECTION 3 Appendix ...