Installation 3
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
39 of 146
9
Press 2 on the upper-control-pad to select the TEST ZONE option for PANEL OUTPUTS: -OFF.
TEST ZONE: 1
>PANEL OUTPUTS: - OFF
Use Up/Down arrow keys to select.
Press > to proceed. Press < to go back.
10
Press 1 on the upper-control-pad to set PANEL OUTPUTS: - ON.
11
Press 2 on the upper-control-pad to select the TEST ZONE option for Loop OUTPUTS: - OFF.
TEST ZONE: 1
>Loop OUTPUTS: - OFF
Use Up/Down arrow keys to select.
Press > to proceed. Press < to go back.
12
Press 1 on the upper-control-pad to set Loop OUTPUTS: - ON.
13
Press 2 on the upper-control-pad to display the test mode for the TEST ZONE:
START TEST MODE ?
TEST ZONE: 1
Test Mode will expire after 15 minutes if zone is idle.
Press ENTER to start Test Mode.
Press EXIT to quit.
Press < to go back.
14
Press ENTER on the upper-control-pad to begin the test or press EXIT to quit.
Test mode runs for 15 minutes.
During the test:
•
The “On Test” LED illuminates continuously
•
The More events LED illuminates continuously
•
The General Trouble LED blinks.
•
The internal buzzer sounds intermittently
The front-panel display provides the following message:
ZONES IN Alarm=000 TRBL=0001 DISAB=0000
* TROUBLE *
NODE=1 AUTOLEARN
Test mode
More Events
15
Press ENTER (again) to cancel the test.