Specifications A
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
70 of 146
Battery and Power
Cabling Construction
Operating Environment
Physical Specifications
Designation
Terminal
Wire Range
Description
NET OUT
32 and 33
14 - 26 AWG
Terminals connections for the eNET “OUT” network
NET IN
34 and 35
14 - 26 AWG
Terminals connections for the eNET “IN” network
COMMS
36 and 37
14 - 26 AWG
Terminal connections for RS485 serial communication
SLC2 OUT
38 and 39
14 - 26 AWG
Terminal connections for the “OUT” of SLC loop 2.
SLC2 IN
40 and 41
14 - 26 AWG
Terminal connections for the “IN” of SLC loop 2.
Designation
Terminal
Wire Range
Description
Battery
Connection
+
12 - 24 AWG
Positive connection for the Standby-batteries
-
12 - 24 AWG
Negative connection for the Standby-batteries
AC Power
L
12 - 24 AWG
Line connection
N
12 - 24 AWG
Neutral connection
E
12 - 24 AWG
Ground connection
Material
All field wiring should be installed using fire rated cables according to the
NFPA.
Cross Sectional Size
The cross sectional size of the SLC cables should be determined based on
length and the number of devices in use. Connect SLC cabling using a
minimum of 1mm cross sectional area.
Low Temperature
32 +/- 3
o
F (0 +/- 2
o
C)
Dry indoor use only
High Temperature
120+/- 3
o
F (49 +/- 2
o
C)
Dry indoor use only
Relative Humidity
93% +/- 2% @ 90 +/- 3
o
F
(32 +/- 2
o
C)
This device functions in an
atmosphere of relative humidity up
to 93 percent, non-condensing.
Dimensions
18.50”H X 14”W X 4.25”D
Mounting
0.25” Maximum screw diameter