![VES Elite-RS H-Series Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/ves/elite-rs-h-series/elite-rs-h-series_installation-manual_1008675033.webp)
Installation 3
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
23 of 146
AC Wiring
Connect cabling from the power source to the terminal-connector for AC Power. The AC Power terminal-connector
is located on the bottom-right of the Elite-RS Panel.
Protect source connections to the AC Power terminal-connector with a 20 Amp fuse. Complete cabling to the AC
Power terminal-connector using three insulated wires that are black, white and green.
Reference Appendix A, Specifications for the wire-gage requirements of these connections.
To wire the terminal-connector:
1
Remove the terminal-connector from the AC Power connection of the Elite-RS.
2
Orient the terminal-connector with the screw-heads facing up.
Figure 3-14
Orienting the AC Terminal-Connector
3
Cut 3 feet of black wire and strip 1/4” of insulation from one end.
4
Insert the stripped end of the black-wire in the left-side of the connector.
5
Tighten the left-screw so that the black-wire is secure in the terminal-connector.
6
Cut 3 feet of white-wire and strip 1/4” of insulation from one end.
7
Insert the stripped end of the white-wire in the right-side of the connector.
8
Tighten the right-screw so that the white-wire is secure in the terminal-connector.
9
Cut 3 feet of green-wire and strip 1/4” of insulation from one end.
E E
P2
R
P2T
L2
R
L2
T
P1
R
P1T
L1
R
L1
T
Alarm
Silence
Panel Sounder
Silence
Lamp
Test
Reset
Fire Drill
Programmable
Function
Enable Access
Re-Sound
Alarm
Fire
AC Power On
Pre-Alarm
On Test
More Events
General
Disablement
General Trouble
Power Trouble
Supervisory
NAC Trouble
More
Fire Events
More
Events
Enter
Exit
24V OUT AUX 24V
+ -
+ -
NC C NO
TROUBLE
NC C NO
FIRE
NC C NO
SUPERVISORY
NAC 1 NAC2
+ -
+ -
NET OUT NET IN
+ -
+ -
COMMS
+ -
SLC1 OUT SLC1 IN
+ -
+ -
Battery
Connection
+
-
JP1
PC
PC / Dialer
Reset
Watchdog
Operated
Contrast
Watchdog
Reset
SLC2 OUT SLC2 IN
+ -
+ -
1
2
3
4
?
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
38 39 40 41
Panel Sounder
Silenced
Delay Active
AC POWER
L N E
AC POWER
L N E
Terminal-connector
connected to front-panel
Terminal-connector removed
from front-panel and rotated
with screw-heads facing up