Front-Panel Menu 4
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
51 of 146
View & Restore Disabled Features
To cancel disablements, scroll through the menu options and toggle disablements to the normal condition.
Another way to cancel disablements is to use the View / Restore Disablements option to scroll through active
disablements and individually enable each disablement by pressing the Enter button.
View Devices
This menu option is used by experienced personnel to investigate system status and may help in fault finding.
The View Devices option displays addresses connected to each detection circuit. For each address & sub-address, the
LCD status display provides the device type, zone and location text.
Analog devices are displayed in the menu with indicators representing the connected device. Digital input devices
such as the points of manual pull stations and switch monitor units are displayed as Normal or Activated. Output
devices are displayed as either Off, Intermittent or Continuous.
Status conditions are displayed in the Devices By Loop or View Devices By Zone area of the menu.
Test Zones
Each zone may be individually put into a Test Mode condition.
Test Zone (1 – 500)
When test mode is selected, devices in the zone may be tested and the Elite-RS Panel will automatically reset after
3 seconds. When a zone is put into test mode, the user is prompted to select a number of test mode options. These
options are retained for each zone, but may be changed at any time.
Local NAC On – Off (Default = On)
When set to the ON position, all NAC outputs will sound for the duration of the fire event. The NACs will be silenced
when the panel automatically resets.
NAC devices may not activate within the three second fire period on systems operating high numbers of
loop-powered NAC devices. Loop confirmation of these NAC devices may be intermittent under these conditions.
Loop Outputs On – Off (Default = Off)
When selected in the ON position, all loop driven outputs other than the loop NAC outputs will operate in accordance
with their standard configuration.
Start Test Mode?
Initiate zone testing using this screen after setting parameters in Test Zone (1 – 500), Local NAC On – Off,
Panel Outputs On – Off and Loop Outputs On – Off.
The screen display is:
A 15 minute timer begins decrementing when a zone is set in test mode. The test will automatically stop after the
timer stops. The timer automatically resets to 15 minutes whenever a device is activated in the zone test.
Test Mode will expire after 15 minutes
if zone is idle.
Press ENTER to start Test Mode.
Press EXIT to quit.
Press < to go back,