Front-Panel Menu 4
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
53 of 146
Fire Event
In the event of a fire, the red FIRE lamp and the appropriate Fire Zone indicator flash (if connected). Details of the
fire activation (address and location text) display on the front-panel.
Fire warning NACs sound throughout the building and the panel fire relay contact energizes.
The panel buzzer pulses, but can be silenced by pressing the Silence Buzzer button.
To silence fire NACs, press any of the menu navigation buttons and enter the Access 2 password then press the Enter
button. Panel controls will be enabled and will remain enabled for one minute after pressing the last key. Pressing the
Alarm Silence button will silence the NACs. The NACs can be started again by pressing the Re-Sound Alarm button.
The system can be reset by pressing the Reset button.
Press the More Events button on the front-panel to display the status of more than two fire events.
The maximum Fire event delay setting shall be less than 10 seconds.
Trouble Event
If there is a fault on the system, the yellow General Trouble indicator will flash and there may be other fault LED
indications which identify the nature of the fault. The Fault Contact and Fault Routing outputs will energize and the
panel buzzer will sound continuously.
Details of the fault will be provided on the front-panel display. The panel buzzer can be silenced at any time by
pressing the Silence Buzzer button.
Press the More Events button on the front-panel to display the status of more than two fire events.
The maximum Trouble event delay setting shall be less than 120 seconds.
Pre-alarm Event
Sensors or inputs can generate a pre-alarm. A pre-alarm is used to warn of a slow change in the analog level of
detection devices. A smoldering fire can be an example of a condition that can cause a pre alarm event. When a
pre-alarm is generated, the control panel will illuminate the pre-alarm LED and will sound the internal buzzer
continuously. The address and location of the source of the pre-alarm will be indicated in the LCD status display.
The source of the pre-alarm input should be investigated. The panel buzzer can be silenced at any time by pressing
the Silence Buzzer button.
Press the More Events button on the front-panel to display the status of more than two fire events.
The maximum Pre-Alarm event delay setting shall be less than 60 seconds.
Access Level 3
Access Level 3 of the Elite-RS Panel provides menu settings for:
•
Edit Configuration
•
Set Times
•
View Event Log
•
System Disablements
•
Loop Data Test