Access Level 2
Access Level 2 provides functions for:
•
Disablements
•
View Devices
•
Test Zones
•
Set System Time
•
Sensor Maintenance Early Warning
•
Access Level 3
Disablements
The Disablements Menu provides an option for viewing and restoring disabled features as well as setting
timed or un-timed disablements for loops, zones, addresses, audible devices and panel I/O:
The timed function provides a disablement-duration of 30 minutes to 24 hours and stops the disablement when the
duration-time expires. The un-timed function provides an infinite disablement that stops when “cleared” on the menu.
Disable Loops
The DISABLE Loops function disables loop-devices from reporting fire signals to the Elite-RS Panel.
This function does not disable loop-devices from reporting trouble and supervisory signals to the Elite-RS Panel.
Disable Zones
All detection devices, including manual pull stations, are disabled in the selected zone.
When a device is disabled, the Elite-RS Panel ignores the analog value reported by the device. All other faults for the
device such as missing device, double address, internal fault, type changed and bad data are still reported by the
Elite-RS Panel.
MAIN MENU - V07.0007H
>DISABLEMENTS
VIEW DeviceS
TEST ZONES
SET SYSTEM TIME
SENSOR MAINTENANCE EARLY WARNING
ACCESS LEVEL 3
DISABLEMENTS MENU
>DISABLE Loops
DISABLE ZONES
DISABLE ADDRESSES
DISABLE AUDIBLE DeviceS
DISABLE PANEL I/O
VIEW & RESTORE DISABLED FEATURES
CAUTION!
The DISABLE Loops function does not isolate the Elite-RS Panel from SLC connections.
Disconnect SLC connections to the Elite-RS Panel when troubleshooting or when performing wiring changes.