Specifications A
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
66 of 146
NAC Outputs
Reference Appendix B, “Equipment List” for NAC devices that are authorized for use with the Elite-RS Panel.
NAC outputs of the Elite-RS Panel can be operated in regulated or special application modes.
Regulated Outputs
NAC outputs of the Elite-RS Panel operate in a regulated mode when conforming to specific levels of
continuous or pulsed DC. NAC outputs meet requirements for regulated levels when the output current does not
exceed the constraints described below:
Continuous Current
Continuous DC currents cannot exceed 1.6 A from either NAC output when operating in a regulated output mode:
Regulated continuous DC output = 1.6 A
NAC 1
+ 1.6 A
NAC 2
= 3.2 A total
Pulsed Current
Pulsed DC currents cannot exceed 900 mA from either NAC output when operating in a regulated output mode:
Regulated pulsed DC output = 900 mA
NAC 1
+ 900 mA
NAC 2
= 1.8 A total
Synchronization
Synchronize the regulated output of NAC 1 and NAC 2 using UL listed and compatible synchronization
modules. Connect End-Of-Line-Device VF1539-00 to the output of each Synchronization Module installed.
Reference Appendix B, Equipment List for more information about NAC synchronization on the Elite-RS Panel.
Special Application Output
NAC outputs of the Elite-RS Panel operate in a special application mode when conforming to specific levels of
continuous DC. NAC outputs meet requirements for special application levels when the output current does not
exceed the 2.3 A of NAC 1 or NAC 2 with the combined current of NAC 1 and NAC 2 not to exceed 3.1 A.
Synchronization
The Elite-RS Panel provides internal device synchronization between the outputs of NAC 1 and NAC 2 when
operating NAC devices from Gentex, Amseco, System Sensor or Wheelock.
External synchronization modules must not be used on the NAC outputs when operating in the
special application mode.
Reference Appendix B, Equipment List for more information about NAC synchronization on the Elite-RS Panel.
Terminal
Connection
Rating
15
NAC 1 (+)
Regulated: 24 VDC @ 1.6 A continuous DC or 900 mA pulsed DC
Special Application: 24 VDC @ 2.3 A continuous with the combined current
of NAC 1 and NAC 2 not to exceed 3.1 A
16
NAC 1 (-)
17
NAC 2 (+)
Regulated: 24 VDC @ 1.6 A continuous DC or 900 mA pulsed DC
Special Application: 24 VDC @ 2.3 A continuous with the combined current
of NAC 1 and NAC 2 not to exceed 3.1 A
18
NAC 2 (-)