Installation 3
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
18 of 146
Operating Constraints
Installation of the FACP must include the operating constraints of the system to maintain continuous signal
monitoring and reporting. Operating constraints are based on the current-driving capability of the Elite-RS outputs
and the external loading caused by devices and cabling.
External loads connected to the Elite-RS outputs must be chosen within the driving limits of each output. The
loading placed on these outputs can be caused by individual or multiple combinations of signaling line circuits,
notification appliances and initiating devices. Cabling is also an external loading property on the Elite-RS outputs.
Select cabling size and length based on the type of circuit connected to the output of the Elite-RS Panel.
Reference Appendix A, Specifications and Appendix C, Calculations to determine specific operating constraints for
devices and cabling connected to the Elite-RS Panel.
Mounting the Elite-RS Panel
Select a mounting location that provides adequate room for opening the door of the Elite-RS Panel.
Provide a minimum of 1” clearance beyond the door-edge when anchoring the Elite-RS Panel.
Figure 3-1
Door Clearance Recommendation
Marking the Location
Mark hole locations on the premises-wall for mounting the Elite-RS Panel.
Figure 3-2
Hole Marking Requirements
1
24.5
12.25
16.50
Ø0.25