Communications Format F
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
112 of 146
Suspending Reporting
Incidents may arise where dialer configurations are calling an incorrect telephone number. While programming
locally through Loop Explorer can directly and quickly correct this situation, sometimes panels are downloaded
remotely. Waiting for the dialer to make many attempts to dial a bad telephone number before releasing the line
can be time consuming.
By going into level 3 <Edit Configuration < Edit I/O < Set Remote Configuration <Enable, the panel will go into a
trouble condition, and delete all messages queued for transmission. This procedure will allow line 1 to be free for an
incoming call. The panel will remain in this trouble condition for 20 minutes or the receipt of a new configuration,
whichever comes first.
All messages that were deleted when the remote configuration mode was entered will never be sent to the monitoring
center, although these signals are stored in the event history log of the panel.