The JA-182ST wireless combined smoke and heat detector

 

The JA-182ST wireless combined smoke and heat detector 

1/2 

MZZ21603 

The JA-182ST is a wireless component of the JABLOTRON 

ALARMS security system. It is used to detect fire hazards in the interior 
of residential or commercial buildings. It is not designed to be installed 
in industrial premises. The JA-182ST detector uses wireless 
communication and it is powered with three AA 1.5V alkaline batteries. 

The JA-182ST consists of two independent detectors – an optical 

smoke detector and a heat detector. The optical smoke detector works 
on the principle of scattered light and is very sensitive to large dust 
particles which are present in dense smoke. It is less sensitive to 
smaller particles generated by the combustion of liquids such as 
alcohol. That is why there is also a built-in heat detector which has a 
slower reaction but is much better at detecting fire which generates 
heat quickly with a small amount of smoke. The microprocessor 
performs digital analysis of these values which markedly increases 
false alarm immunity.

 

Detector range 

The smoke detector must be installed so that any smoke easily drifts 

into the detector, e.g. on the ceiling. It is suitable for residential buildings 
but not suitable for free spaces, outdoor environments or interiors with 
extremely high ceilings (above 5 m) where fire by-products can 
disperse over a large area – the smoke would not reach the detector 
position. 

The detector must always be placed in the section leading to the exit 

of the building (escape route), see Figure 1. If the building has a floor 
area greater than 150 m2, installation of an additional detector in some 
other suitable place is required, see Fig.2.

 

1

2

3

3

4

 

Fig 1 

2

1

3

3

4

3

 

Fig 2 

1 - kitchen 
2 - living room 
3 - bedroom 
4 - children’s bedroom 

 

- Basic security 

- For more security 

 

 

1

3

3

3

 

Fig 3 

For large buildings it is recommended to place additional detectors in 

rooms where people sleep and in rooms with an increased risk of fire - 
see Fig.3.  

Installation on level ceilings 

Place the detector in the centre of the room if possible. The detector 

must not be recessed into the ceiling due to the possible existence of a 
cool air layer on the ceiling. 

Never place the detector in the corner of 

the room though

 (always keep at least a 0.5 m distance from the 

corner) see Fig 4. 

Installation on sloping ceilings

 

If the ceiling is not suitable for mounting on a level surface (e.g. a 

room under a roof ridge), the detector can be installed as in Fig. 5

 

0.5m

TOP

 

Fig 1 

 
 

0,9 m

 

 

Fig 2 

 centre of the room, best location 

  acceptable location 

Walls, partitions, barriers and lattice ceilings

 

The JA-182ST detector must not be installed closer than 0.5 m 

from any wall or partition

. A narrow room with a width of less than 

1.2m requires the detector(s) to be placed at a distance of at least one 
third of the room’s width away. In the case of separating walls 
(partitions, warehouse objects) which do not reach the ceiling, 

the 

space is considered to be fully separated if the gap between the 
top of the separating wall and the ceiling does not exceed 0.3 m

A free space of at least 0.5 m is required under the detector. Any 
irregularities of the ceiling (e.g. girders) exceeding 5 % of the ceiling 
height shall be considered a wall and the above mentioned limitations 
shall apply. 

Ventilation and air circulation 

The detectors must not be installed directly by a fresh air inlet (e.g. 

air conditioning vents). 

In the case of air being supplied through a 

perforated ceiling, each detector must be placed so that no perforation hole 
occurs within 0.6m of the detector. 

Avoid installing the detector in the following locations: 

  places with poor air circulation (niches, corners, apexes of A-shaped 

roofs, etc.) 

  places exposed to dust, cigarette smoke or steam 

  places with over-intense air circulation (close to ventilators, heat 

sources, air conditioning outlets, etc.) 

  in kitchens and other cooking places (because steam, smoke or oily 

fumes can reduce detector sensitivity). 

  beside fluorescent lights (electrical interference can cause a false alarm) 

  in areas with lots of small insects 

Please note: Most false alarms are caused by improper 

detector location. 

See CEN/TS 54-14 standards for detailed installation guidelines. 

Installation

 

The detector should be installed by a trained technician with a valid 

certificate issued by an authorized distributor. Abide by the procedures 
recommended in the previous paragraphs. 

1

2

3

1400- 00- 0000- 0001

5

4

6

INS

MEM

SMOKE
TEMP

+

-

7

 

Fig 6: 

1– detector cover opening; 2 – detector cover closing; 3 – optical 

status signalling; 4 – arrow showing where to insert the detector;  

5 – enrollment code; 6 – configuration terminals; 7 – battery holders  

1.  open the detector cover, by turning it anti-clockwise (1) 
2.  attach the removed plastic base to the desired place with 

screws (not shown above). 

3.  set the configuration terminals (6) according to the table below: 
4.  Proceed according to the control panel installation manual. 

Basic procedure: 
a.  There must be a JA-110R radio module installed in the 

control panel. Go to the F-Link program, select the required 
position in the Devices window and launch the enrollment 
mode by clicking on the Enroll option.  

b. When you insert all batteries into the detector, the 

enrollment code is sent to the system – its sending is 
confirmed with a short flash of the LED indicator (3). The 
default control panel reaction to the signal of the detector is 
Fire. 

5.  Insert the detector into the plastic base. The detector can be 

inserted in the plastic base in one position only. It is marked 
with arrows (4) on both plastic parts. Close the detector cover 
by turning it clockwise (2).  

Note

: The detector can also be enrolled into the system by entering 

its enrollment code (5) in the F-Link program. (1400-00-0000-
0001). 

Detector setting 

The detector properties can be set in the 

Detectors

 window in 

the 

F-Link

 program and with the configuration terminals. The 

Reaction option in the Detectors window allows you to set the type 
of reaction of the system to the activation of the enrolled detector.  
The configuration terminals directly on the detector PCB determine 
other properties: 