Troubleshooting
SLC Trouble Finding
The Velocity panel will monitor the SLC for open or short circuit faults. The panel’s SLC isolator monitors for both open and short circuit
faults; the faults are reported as ISOLATOR FAULTS along with a description. The faults reported are:-
Break in +ve wire
To help locate a +ve cable break, re-run
the SLC loop search, and check the
detailed loop report after the search is
complete.
In this example, the break is between
address 154 (which is seen from side A
only), and address 155 (which is seen from
side B only)
(This only applies if the loop is addressed
sequentially)
If a system uses spurs
(Not recommended
for more than a few devices)
, a cable break
in the spur will not be seen. Look for
missing device addresses in the loop
report.
Break in -ve wire
Use the same method as above to locate a
–ve break.
Short circuit on side A
If the panel reports a loop short side A ,
then there is a short circuit fault on the
SLC, somewhere between the panel (side
A), and the first device with a short circuit
isolator on the loop.