Velocity Operation Manual
www.velocitydetection.com
51
Next, we will add a cause and effect that will ensure
that a subsequent actuation of alarm initiating
devices on another initiating zone of the system
shall result in the activation of all the outputs.
Finally, in this example we will use a key switch
connected to a VDOT-DIP-SCI
(Addressable Dual
Input Module with SCI)
at address Loop: 1 Point 2,
to allow manual activation of the general alarm
evacuation signal.
This flow chart is a breakdown of the pre-signal
operation that has been programmed into the
Velocity MMP cause & effects.
When finished, press the exit icon
. The panel
will ask if you want to save the changes.
Press tick
to save the changes, or press to
discard.
Multiple detector operation will now be
programmed, and ready for testing.