Velocity Operation Manual
www.velocitydetection.com
7
Alarm Condition
The following functions will be performed when in the
alarm condition:
•
Will cause the panel’s internal buzzer to sound with
a steady output.
•
The Alarm LED will illuminate and flash.
•
The LCD displays the Alarm along with the device
name, type, address, associated zones and
time/date.
•
Alarms latch and are not allowed to clear
automatically.
•
Alarms activate cause & effects if programmed.
•
Alarm relays are activated.
•
The trouble relays are not activated.
•
Stores event in history log and sends message to
printer.
A typical alarm display would be as illustrated below:
On the screen, the panel shows:
•
Fire Icon
•
Number of zones in alarm
•
Number of devices in alarm
•
First & last zones in alarm
•
Details of alarms in chronological order (showing device
type, Zone number & label, Device address & label)
•
Scroll arrows for displaying further events
Supervisory Condition
The Supervisory condition can be configured as latching
or non-Latching for each supervisory input.
The following functions will be performed when in the
supervisory condition:
•
Will cause the panel’s internal buzzer to sound with
a pulsed output.
•
The system Supervisory LED will illuminate and
flash.
•
The LCD displays the Supervisory status label along
with the device name, type, address, associated
zones and time/date.
•
Any supervisory relays are activated.
•
The alarm relay is not activated.
•
Silenced alarms are not resounded.
•
Stores event in history log and sends message to
printer.
If the supervisory input is configured as non-latching,
and there are no active trouble or alarm events, when
the supervisory event clears, the screen will clear.
If the supervisory input is configured as latching , when
the supervisory event clears, the screen will display Local
supervisory off, and the panel will need to be reset to
clear the screen.
A typical supervisory display would be as illustrated below:
On the screen, the panel shows:
•
Supervisory Icon
•
Number of supervisory events
•
Details of supervisory in chronological order (showing type,
zone number & label, device address & label)
•
Scroll arrows for displaying further events