Velocity Operation Manual
www.velocitydetection.com
34
An AND / OR cause will request more inputs before
activating the output.
Select up to 8 causes. Press the OUTPUT icon when
finished.
After selecting the input cause(s), the panel displays a
screen to select the following effect options:
Panel address:
Leave as zero if the output effect is on this local panel,
otherwise set to the network address of the destination
panel.
Output retrigger:
This defines whether the sounders will resound from a
new alarm if they had been previously silenced.
The options are:-
•
Never
resound
•
Resound on an alarm from a
New zone
•
Always
resound for any new alarm.
Select the output type (Point, Local I/O, zone or Panel).
Depending on the OUTPUT type chosen, the panel will
display a list of sub options. For ‘
Point’
effects, the
options are:-
•
Day Delay:
0-600 seconds
•
Night Delay:
0-600 seconds
(This is the delay used if Day/Night timer is not set)
•
Point Effects:
Evacuation
Warning
Beacon
Switch OFF
Enable
Disable
•
Loop number:
1-26
•
Point address:
Device Loop Address: 1-254
Device Port: 0-15 (Select 0 for all ports)