Velocity Operation Manual
www.velocitydetection.com
56
When global relays have been disabled, the LCD display
changes from SYSTEM NORMAL to Disablement, as
shown.
The screen shows the number of relay output interfaces
disabled.
The General Disablement LED will be lit.
Details of the disabled relay outputs can be viewed by
pressing the disabled loop devices icon
or the
disabled local I/O icon
. If any zones have all of their
outputs disabled, it will be indicated by the disabled zone
outputs icon
.
To re-enable the relay status, press the ‘Enabled’
selection area. The text will change from ‘All disabled’ to
‘All Enabled’ for relay status.
Press the exit icon
. The panel will ask if you want to
save the changes.
Press tick
to save the changes, or press
to
discard.
Change the global mode for sounder status to disable by
pressing the ‘Disabled’ selection area. The text will
change from ‘All enabled’ to ‘All disabled’ for sounder
status.
This will disable
ALL
panel sounder output interfaces.
Press the exit icon
. The panel will ask if you want to
save the changes.
Press tick
to save the changes, or press
to
discard.
When sounder status has been disabled, the LCD display
changes from SYSTEM NORMAL to Disablement. The
screen shows:-
The number of disabled SLC sounder devices.
The number of disabled NAC outputs.
The General Disablement and NAC Disablement LED will
be lit
If there are any output relays on the system that are not
disabled, the Disabled Alarm Group icon will not be
displayed.
If there are no relays fitted, or if the relays have been
disabled as well , the Disabled Alarm Group icon will be
displayed