Velocity Operation Manual
www.velocitydetection.com
54
SLC Device Disablement
Rather than disable an entire zone, it is often useful to just disable one or more devices or points (detector, call point, interface or
sounder) within a zone, especially if they are malfunctioning and likely to cause an unwanted alarm or repeatedly indicate a trouble
condition.
Enter the Engineer
or User password
, Press
the menu access icon, and select the Point icon
.
(The disabling function is available to engineer & users).
The panel shows the Point menu.
Press on the ‘Mode’ field for the device to be
disabled.
Select further devices to disable if necessary, and then
press Exit
to save.
When SLC devices have been disabled, the LCD display
changes from SYSTEM NORMAL to Disablement/Test, as
shown.
The screen shows the number of devices disabled.
The General Disablement LED will be lit, but the zonal
disablement LEDs will not light, unless all devices in that
zone have been disabled.
Note: If an input on a module is in the same zone as loop
devices, the loop devices, and the module inputs will
need to be disabled before the Zone disabled indication
appears.
Details of the individual SLC devices disabled can be
viewed by pressing the ‘Disabled loop devices’ icon
.