Velocity Operation Manual
www.velocitydetection.com
45
The panel shows the Delays screen.
See the ‘Alarm Verificat’ with Off & On options.
Select ON to enable, or select OFF to keep the
verification disabled.
The ‘Retard Time’ is the duration that the alarm signal is
initially delayed and can be configured between 1-30
seconds.
To change the time, press either the + or – button to
increase or decrease the zone number.
You can also type in the number via the panel numerical
keyboard, to do this press on the zone number field.
Type in the required zone number and press the green
tick to confirm.
The ‘Period Time’ is the confirmation time after the
delay and can be configured between 1-60 seconds.
To change the time, press either the + or – button to
increase or decrease the zone number.
You can also type in the number via the panel numerical
keyboard, to do this press on the zone number field.
Type in the required zone number and press the green
tick to confirm.
When finished, press the exit icon
. The panel will
ask if you want to save the changes.
Press tick
to save the changes, or press to discard.
When a smoke detector has entered the alarm
verification sequence, the panel will display an onscreen
message to indicate that an alarm is currently being
verified accompanied with a zone and device address.
At the same time, the smoke detector that is currently in
the alarm verification sequence will light up its alarm
LED’s while it is in the RETARD phase.
The panel will record this verification event and store it
in the event log.