Velocity Operation Manual
www.velocitydetection.com
4
•
Off if the panel re-enters alarm, the system is reset, or if a drill is carried out.
e)
LED: Power
•
Green LED.
•
On steady when the panel has power.
•
Off when the panel has no source of power applied.
f)
LED: Controls Active
•
Yellow LED.
•
Indicates that the user now has access to use either the function buttons or the LCD touchscreen display (depending on
access level).
•
On when the user has entered the access level 2 user password, or when the user has entered the access level 3
engineers password.
•
Off when either the access has timed out, or when the user/engineer has locked the panel.
g)
LED: Acknowledge
•
Yellow LED.
•
Flashes when there are unacknowledged events.
•
On steady when all current events have been acknowledged.
•
Off when there are no events.
h)
LED: General Disablement
•
Yellow LED.
•
On steady when any part of the system has been disabled.
•
Off when there are no current disablements.
i)
LED: General Test
•
Yellow LED.
•
On steady when any part of the system is in test mode.
•
Off when there are no current circuits/devices in test mode.
j)
LED: NAC Trouble/Disablement
•
Yellow LED.
•
On steady if there is a fault detected on an NAC circuit.
•
On steady when an NAC has been disabled.
•
Off when the NAC’s are in the normal condition.
k)
LED: NAC Delay
•
Yellow LED.
•
On when an NAC has been configured to delay its output.
•
Off when there is no configured delay to the NAC’s output.
l)
LED: NAC Active
•
Red LED.
•
On when the output of any NAC is currently active.
•
Off when there are no NAC’s with their outputs active.
m)
LED: CPU Trouble
•
Yellow LED.
•
On when there is an abnormal microprocessor running condition due to various unexpected phenomena.
•
Off when the microprocessor is running correctly.
n)
Function Button: Silence Alarm
•
A minimum of Level 2 access (By entering the user password) is required.
•
When the
SILENCE ALARM
key is pressed, the panel’s Notification Alarm Appliances will be silenced.
•
The
Alarm Silenced LED
will start flashing and remain until either the panel is reset, or until another alarm retriggers the
notification appliances. The
RED ALARM LED
shall be maintained.
•
NOTE: to silence the panels internal buzzer, the alarm must be acknowledged.
•
It also sends a SILENCE SOUNDERS’ message to the printers and history log.
o)
Function Button: ACK (Acknowledge)