Monitoring menu
vacon • 85
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
V2.6.6
DIN StatusWord2
1
57
16-bit word where each bit represents the status
of one digital input. 6 digital inputs from every slot
are read. Word 1 starts from input 5 in slot C (bit0)
and goes all the way to input 6 in slot E (bit13).
V2.6.7
MotCurrent1 deci.
0.1
45
Motor current monitor value with fixed number of
decimals and less filtering. Can be used e.g. for
fieldbus purposes to always get the right value
regardless of frame size, or for monitoring when
less filtering time is needed for the motor current.
V2.6.8
FreqRef Source
1
1495
Shows the momentary frequency reference
source.
0=PC
1=Preset Freqs
2=Keypad Reference
3=Fieldbus
4=AI1
5=AI2
6=AI1+AI2
7=PID Controller
8=Motor Potentiom.
9=Joystick
10=Inching
100=Not defined
101=Alarm,PresetFreq
102=Autocleaning
V2.6.9
LastActiveFaultCode
1
37
The fault code of latest activated fault that has not
been reset.
V2.6.10
LastActiveFault ID
1
95
The fault ID of latest activated fault that has not
been reset.
V2.6.11
LastActiveAlarmCode
1
74
The alarm code of latest activated alarm that has
not been reset.
V2.6.12
LastActiveAlarm ID
1
94
The alarm ID of latest activated alarm that has
not been reset.
V2.6.13
MotorRegulat.Status
1
77
Motor limit controller status. Checked = limit con-
troller is active, Unchecked = limit controller is
not active
Table 50. Advanced values monitoring
Code
Monitoring value
Unit
Scale
ID
Description