Parameters
vacon • 133
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.15.2
Group 3.14.2: Setpoints
Table 116. External PID-controller, setpoints
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.14.2.1
Keypad SP 1
0.00
100.00
Varies
0.00
1640
P3.14.2.2
Keypad SP 2
0.00
100.00
Varies
0.00
1641
P3.14.2.3
Ramp Time
0.00
300.00
s
0.00
1642
P3.14.2.4
Setpoint Selection
Varies
Varies
DigIN
Slot0.1
1048
FALSE = Setpoint 1
TRUE = Setpoint 2
P3.14.2.5
SP 1 Source
0
22
1
1643
0 = Not Used
1 = Keypad Setpoint 1
2 = Keypad Setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 =ProcessDataIn1
10 =ProcessDataIn2
11 =ProcessDataIn3
12 =ProcessDataIn4
13 =ProcessDataIn5
14 =ProcessDataIn6
15 =ProcessDataIn7
16 =ProcessDataIn8
17 = Temperature Input 1
18 = Temperature Input 2
19 = Temperature Input 3
20 = Temperature Input 4
21 = Temperature Input 5
22 = Temperature Input 6
AI’s and ProcessDataIn are han-
dled as percent (0.00-100.00%)
and scaled according to Set-
point minimum and maximum.
NOTE:
ProcessDataIn signals
use 2 decimals.
P3.14.2.6
SP 1 Minimum
-200.00
200.00
%
0.00
1644
Minimum value at analogue sig-
nal minimum.
P3.14.2.7
SP 1 Maximum
-200.00
200.00
%
100.00
1645
Maximum value at analogue
signal maximum.
P3.14.2.8
SP 2 Source
0
22
0
1646 See P3.14.2.5.
P3.14.2.9
SP 2 Minimum
-200.00
200.00
%
0.00
1647
Minimum value at analogue sig-
nal minimum.
P3.14.2.10
SP 2 Maximum
-200.00
200.00
%
100.00
1648
Maximum value at analogue
signal maximum.