vacon • 182
Parameters
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
P3.24.1.5
AC O
FF
AT
S
TOP
D
ELAY
Delay to switch AC Off at stop, if it happened with AC On condition.
Mode 0 Always active
In mode 0, relay for AC supply is always On when pump is running. There are two possible condi-
tions, to switch the relay On.
P3.24.2.1
AC O
N
C
ONDITION
At Run: as AC switch relay is Off at power-on, the drive must start from PV modules supply, after
that the relay is immediately switched On. AC grid backup will avoid further stops, in case of low
power from modules.
At Start: external Start signal is sufficient condition to switch the relay On and connect to AC grid.
This can happen also if the drive is powered up with only backup 24V on control board.
Mode 1 Irradiation
In mode 1, relay for AC supply is managed accordingly to measurement of irradiation from analogue
signal.
There is an absolute minimum threshold for switching On, and an offset added to this as threshold
to switch Off.
AC relay is switched On also in case of Low Power alarm at start or Undervoltage fault.
With AC connected, MPPT will reach the maximum motor speed. Power is shared between AC grid
and PV modules, according to their actual capacity.
In this condition, DC voltage stays naturally close to rectified AC voltage (V3.24.1.1).
DC voltage will increase in case the modules can sustain the needed full power.
When switching Off condition is reached (high irradiation), motor speed is decreased until DC volt-
age increases above (V3.24.1.1 + P3.24.1.4). That is the working point aligned with present power
available from PV module. Relay is switched Off afterwards.
It is possible to activate Identification of minimum irradiation threshold. It means that the value of
parameter is internally adjusted, so that the AC switching On condition always happens when the
motor is close to a programmable speed. This compensates the changeable ratio between irradia-
tion and power, that is function of temperature.
P3.24.3.1
I
RRADIATION
S
IGNAL
Selection between AI1 and AI2.
P3.24.3.2
M
AX
I
RRADIATION
Value of irradiation at maximum signal.
P3.24.3.3
AC O
N
I
RRADIATION
Threshold for irradiation, below which AC relay is switched On.
P3.24.3.4
AC O
FF
I
RRADIATION
OFFSET
Value added to P3.24.3.3 to determine the threshold for switching AC Off.
P3.24.3.5
I
RRADIATION
S
TABILIZATION
T
IME
Irradiation has to stay below/above thresholds for this time, to activate switching On/Off.