vacon • 40
Startup
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
4.2.3
Local/Remote application
Use the Local/Remote application when, for example, it is necessary to switch between 2 different
control places.
To change between the Local and the Remote control place, use DI6. When Remote control is active,
you can give the start/stop commands from Fieldbus or from I/O terminal (DI1 and DI2). When Local
control is active, you can give the start/stop commands from the keypad, Fieldbus or I/O terminal
(DI4 and DI5).
For each control place, you can make a selection of the frequency reference from the keypad, Field-
bus or I/O terminal (AI1 or AI2).
It is possible to configure all the drive outputs freely in all the applications. There are 1 analogue
output (Output Frequency) and 3 relay outputs (Run, Fault, Ready) available on the basic I/O board.
4.2.3.1
M1.33 Local/Remote
Table 16. Local/Remote start-up wizard menu
Code
Parameter
Min
Max
Unit
Default
ID
Description
P1.32.1
I/O B Ref sel
1
9
9
131
Selection of ref source when
control place is I/O B. See
above.
NOTE
: I/O B control place
can only be forced active
with digital input (P3.5.1.7).
P1.32.2
I/O B Ctrl force
DigIN
SlotA.6
343
TRUE = Used frequency ref-
erence is specified by I/O
reference B parameter
(P3.3.1.6).
P1.32.3
I/O B Ref force
DigIN
SlotA.6
411
Force control to fieldbus
P1.32.4
Ctrl signal 1 B
DigIN
SlotA.4
423
Start signal 1 when control
place is I/O B
P1.32.5
Ctrl signal 2 B
DigIN
SlotA.5
424
Start signal 2 when control
place is I/O B
P1.32.6
Keypad Ctrl force
DigIN
Slot0.1
410
Force control to keypad
P1.32.7
Fieldbus Ctrl force
DigIN
Slot0.1
411
Force control to fieldbus
P1.32.8
Ext fault close
DigIN
SlotA.3
405
FALSE = OK
TRUE = External fault
P1.32.9
Ext fault open
DigIN
Slot0.2
406
FALSE = External fault
TRUE = OK