vacon • 98
Parameters
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.4
Group 3.3: References
7.1.4.1
Frequency reference
The frequency reference source is programmable for all control places except
PC
, which always
takes the reference from the PC tool.
Remote control place (I/O A):
The source of frequency reference can be selected with parameter
Remote control place (I/O B):
The source of frequency reference can be selected with parameter
Local control place (Keypad):
If the default selection for parameter P3.3.1.7 is used the reference
set with parameter P3.3.1.8 applies.
Remote control place (Fieldbus):
The frequency reference comes from fieldbus if the default value
for parameter P3.3.1.11 is kept.
Table 65. Frequency reference parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.3.1.1
MinFreqReference
0.00
Hz
0.00
101
Minimum allowed frequency refer-
ence
P3.3.1.2
MaxFreqReference
320.00
Hz
50.00
102
Maximum allowed frequency ref-
erence
P3.3.1.3
PosFreqRefLimit
-320.0
320.0
Hz
320.00
1285
Final frequency reference limit for
positive direction.
P3.3.1.4
NegFreqRefLimit
-320.0
320.0
Hz
-320.00 1286
Final frequency reference limit for
negative direction.
NOTE:
This parameter can be
used e.g. to prevent motor from
running in reverse direction.
P3.3.1.5
I/O A Ref sel
1
9
5
117
Selection of ref source when con-
trol place is I/O A
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
P3.3.1.6
I/O B Ref sel
1
9
9
131
Selection of ref source when con-
trol place is I/O B. See above.
NOTE
: I/O B control place can only
be forced active with digital input
(P3.5.1.7).
P3.3.1.7
Keypad Ref Sel
1
9
2
121
Selection of ref source when con-
trol place is keypad:
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power