Monitoring menu
vacon • 87
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6.1.8
ExtPID Controller
6.1.9
Mainten. counters
6.1.10
Fieldbus data
Table 53. External PID Controller value monitoring
Code
Monitoring value
Unit
Scale
ID
Description
V2.9.1
ExtPID setpoint
Varies
According to
P3.14.1.10
83
External PID controller setpoint value in process
units. Process unit is selected with a parameter.
V2.9.2
ExtPID feedback
Varies
According to
P3.14.1.10
84
External PID controller feedback value in process
units. Process unit is selected with a parameter.
V2.9.3
ExtPID error
Varies
According to
P3.14.1.10
85
External PID controller Error value. Deviation of
feedback from setpoint in process units. Process
unit is selected with a parameter.
V2.9.4
ExtPID output
%
0.01
86
External PID controller outputin percent (0..100%).
This value can be fed e.g. to Analogue output.
V2.9.5
ExtPID status
1
87
0=Stopped
1=Running
4=In dead band
Table 54. Maintenance counter monitoring
Code
Monitoring value
Unit
Scale
ID
Description
V2.11.1
MaintenCounter 1
h/ kRev
Varies
1101
Status of maintenance counter in revolutions multi-
plied by 1000, or hours.
For configuration and activation of this counter, see
chapter Group 3.16: Maintenance counters.
Table 55. Fieldbus data monitoring
Code
Monitoring
value
Unit
Scale
ID
Description
V2.12.1
FB Control Word
1
874
Fieldbus control word used by application in bypass
mode/format. Depending on the fieldbus type or profile
the data can be modified before sent to application.
V2.12.2
FB Speed Refer-
ence
Varies
875
Speed reference scaled between minimum and maxi-
mum frequency at the moment it was received by the
application. Minimum and maximum frequencies can
be changed after the reference was received without
affecting the reference.
V2.12.3
FB data in 1
1
876
Raw value of process data in 32-bit signed format
V2.12.4
FB data in 2
1
877
Raw value of process data in 32-bit signed format
V2.12.5
FB data in 3
1
878
Raw value of process data in 32-bit signed format
V2.12.6
FB data in 4
1
879
Raw value of process data in 32-bit signed format
V2.12.7
FB data in 5
1
880
Raw value of process data in 32-bit signed format
V2.12.8
FB data in 6
1
881
Raw value of process data in 32-bit signed format
V2.12.9
FB data in 7
1
882
Raw value of process data in 32-bit signed format
V2.12.10
FB data in 8
1
883
Raw value of process data in 32-bit signed format